6 | Technical data
STOBER
40
02/2019 | ID 442728.05
6.2.1.2
Power unit: Size 2
Electrical data
PS6A24
U
1PU
3 × 400 V
AC
, +32%/−50%, 50/60 Hz;
3 × 480 V
AC
, +10%/−58%, 50/60 Hz
U
2PU
√2 × U
1PU
P
N,PU
10 kW
I
1N,PU
25 A
I
1maxPU
I
1N,PU
× 180% for 5 s;
I
1N,PU
× 150% for 30 s
C
maxPU
5000 µF
Tab. 16: PS6 electrical data, size 2
6.2.1.3
Power unit: Size 3
Electrical data
PS6A34
U
1PU
3 × 400 V
AC
, +32%/−50%, 50/60 Hz;
3 × 480 V
AC
, +10%/−58%, 50/60 Hz
U
2PU
√2 × U
1PU
P
N,PU
20 kW
I
1N,PU
50 A
I
1maxPU
I
1N,PU
× 180% for 5 s;
I
1N,PU
× 150% for 30 s
C
maxPU
10000 µF
Tab. 17: PS6 electrical data, size 3
6.2.1.4
Parallel connection
The power and current increase if supply modules are connected in parallel. Take into account
that the total is derated by a factor of 0.8 in doing so.
The charging capacity of the supply modules can be increased by a parallel connection only if
the power grid supply is connected to all supply modules simultaneously. Increasing the
charging capacity also requires derating the total by a factor of 0.8.
The following table shows example combinations for parallel connection.
Electrical data
2 x PS6A24
3 x PS6A24
2 x PS6A34
3 x PS6A34
P
N,PU
16 kW
24 kW
32 kW
48 kW
I
1N,PU
40 A
60 A
80 A
120 A
C
maxPU
8000 µF
12000 µF
16000 µF
24000 µF
Tab. 18: Electrical data for parallel connection: Example combinations
Note the general conditions for parallel connection of supply modules in the chapter