18 of 40
Operating Manual:
SU780UE
10207.5
|
7.18.2016
5.1.2 – Control Panel Quick Guide
The Swift GUI menu tree below starts with the default screen (Outlined in the “Basic
GUI Functions” table on Page 19). Buttons provide navigation to the screens on the
next level of the menu tree.
Home
– display current freezer temperature.
•
Setup
– display Password Identification Number (PIN) status, door defrost status,
temperature set point, system date and time and alarm status.
•
Setup
– display temperature set point.
PIN required if enabled.
Change Set Point
– display and change the temperature set point and high
and low temperature limits.
Alarm Setup
– display and change the Temp. Delay (to delay an over tempera-
ture alarm after a door opening), Audible Delay (time interval to silence the
audible alarm upon request), Ext. Delay (to delay remote alarm contact closure
after alarm condition is detected) and Door Delay (period that the door may
remain open without alarm).
Date & Time Setup
– display and change system date and time.
Door Defrost
– adjust defrost heater between 0 to 100 %.
PIN Setup
– disable/enable the system PIN and change the PIN.
•
Silence Alarm
– temporarily silence audible alarm.
•
Event Log
– tracks the last approximately 200 alarm conditions such as door open-
ings, temperature set point changes, over temperature condition, and power outages.
•
Chart History
– displays the cabinet interior air temperature over the last 12 hours,
24 hours or 7 days. Increase the chart resolution by tapping the screen.
•
About
– display freezer model number, serial number, firmware version, engine
number, run hours, temperature set point, and install date.
–
Service
– display cabinet, control and cold-head RTD temperatures, warm-head
thermistor temperature and engine voltage, current and power.
Service screen information is used for service by authorized personnel only.
Service PIN required.
RTD Calibration
– display RTD readings and calibration offsets to apply to
reading (used to compensate for discrepancies between Display RTD and
user-supplied temperature standards).
–
Alarm Test
– tests alarm.
–
Service Contact
– provides phone, email, and web address for manufacturer.