INSTALLATION
Preparation
www.stiebel-eltron.com
WPE-I H 400 Premium |
51
EN
GL
ISH
9.2 Minimum clearances
WPE-I 33 H 400 Premium | WPE-I 44 H 400 Premium
≥500
≥500
≥300
≥500
≥1000
D
00000
82
77
6
f
f
Maintain the minimum clearances to ensure trouble-free op-
eration of the appliance and facilitate maintenance work.
WPE-I 59 H 400 Premium | WPE-I 87 H 400 Premium
≥500
≥300
≥500
≥500
≥1000
D
00000
82
77
7
f
f
Maintain the minimum clearances to ensure trouble-free op-
eration of the appliance and facilitate maintenance work.
9.3 Preparation of the installation site
f
f
Observe chapter “Sound emissions”.
The room where the appliance is installed must meet the following
conditions:
- No risk from frost.
- The room must not be subject to a risk of explosions arising
from dust, gases or vapours.
- When installing the appliance in a boiler room together with
other heating equipment, ensure that the operation of other
heating equipment will not be impaired.
- Load bearing floor (for the weight of the appliance, see chap-
ter “Specification / Data table”).
f
f
Install the appliance, ideally on an external wall.
f
f
Ensure that the substrate is level, even, solid and permanent.
f
f
Install the appliance on a concrete floor with a thickness of at
least 100 mm or on another base with corresponding charac-
teristics.
f
f
For installation on floating screeds, make provisions for quiet
heat pump operation.
f
f
Isolate the installation surface around the heat pump by
means of a recess. After completing the installation, seal the
recess with a waterproof, sound insulating material, such as
silicone.