10.3 Application range
Heating
-30
-20
-10
0
10
20
30
40
0
10
20
30
40
50
60
70
1
D
00000
43
51
5
1 Application range limits
X Outside temperature [°C]
Y Flow temperature [°C]
10.4 Sensor resistance values
pt1000 sensor
pTC sensor
Temperature in °C
resistance in Ω
resistance in Ω
-30
882
---
-20
922
1367
-10
961
1495
0
1000
1630
10
1039
1772
20
1078
1922
25
1097
2000
30
1117
2080
40
1155
2245
50
1194
2417
60
1232
2597
70
1271
2785
80
1309
2980
90
1347
3182
100
1385
3392
110
1423
---
120
1461
---
Note
When measuring with a multimeter, the resistance values
serve only to identify faulty or incorrect sensors. Measur-
ing with a multimeter is too imprecise to test for accuracy.