![STIEBEL ELTRON 223400 Manual Download Page 8](http://html1.mh-extra.com/html/stiebel-eltron/223400/223400_manual_1376689008.webp)
iNSTaLLaTiON
Preparations
www.stiebel-eltron.com
WPL E | WPL cool |
9
9.2.2 Indoor installation
≥500
≥300
≥500
≥500
≥1000
D
00000
19
24
2
f
f
Maintain the minimum clearances to ensure trouble-free op-
eration of the appliance and facilitate maintenance work.
9.3 Preparation of the installation site
General information
f
f
See chapter "Sound emissions".
f
f
Ensure that the appliance is accessible from all sides.
f
f
Ensure that the substrate is level, even, solid and permanent.
9.3.1 Outdoor installation
f
f
Provide a recess (space) in the base to enable supply pipes/
cables to be routed into the appliance from below.
Foundations with recess
4
130
800
50
1240
260
70
1
2
3
d01
d02
D
00000
56
55
8
1
Air discharge
2
Air intake
3
Main wind direction
4
Recess
d01 Heat pump flow
d02 Heat pump return
f
f
Ensure that the foundations offer an adequate recess.
Example: Routing pipes in the base
A
6
8
1
2
7
4
5
3
D
00000
19
23
7
A Depth of frost line
1 Heating circuit flow
2 Heating circuit return
3 Conduit for supply lines/cables
4 Foundation
5 Gravel bed
6 Drainage pipe
7 Condensate drain hose
8 Electrical cables/leads