INSTALLATION
COMMISSIONING
10. Commissioning
!
Material losses
Boiling dry destroys the high limit safety cut-out and the
controller-limiter combination must then be replaced.
!
Material losses
If a heat exchanger is installed in the same cylinder, you
must limit the maximum temperature for this heat ex-
changer. This prevents the high limit safety cut-out of the
threaded immersion heater from responding.
f
f
Fill the system with water.
f
f
Turn the temperature selector to maximum temperature.
f
f
Switch the mains power ON.
f
f
Check the function of the appliance.
f
f
Check the function of the safety assembly.
10.1 Appliance handover
f
f
Explain the appliance function to users and familiarise them
with its operation.
f
f
Make users aware of potential dangers, especially the risk of
scalding.
f
f
Hand over these instructions.
11. Settings
Adjusting the temperature selection limitation
You can adjust the temperature selection limitation beneath the
temperature selector. At the factory, the appliance is limited to
60 °C.
f
f
Isolate the appliance from the power supply.
f
f
Set the temperature selector to “cold”.
f
f
Pull off the temperature selector.
60
°C
45
°C
1
2
26
�0
2�
79
�0
03
4
1 Limiter disc
2 Without limiter disc, maximum 80 °C
f
f
You can set the limit to 45 °C / 60 °C by rotating the limiter
disc. By removing the limiter disc, the maximum temperature
can be set.
f
f
Replace the temperature selector.
12. Troubleshooting
Note
The high limit safety cut-out can respond at temperatures
below –15 °C. The appliance may be subjected to these
temperatures during storage or transport.
fault
Cause
Remedy
The water does not
heat up.
The high limit safety
cut-out has responded
because the controller
is faulty.
Remedy the cause of
the fault. Replace the
controller-limiter com-
bination.
The high limit safety
cut-out has responded
because the temperature
has dropped below -15 °C.
Press the reset button.
The high limit safety cut-
out has responded be-
cause a heat exchanger
in the same cylinder is
set too high.
Limit the maximum
temperature of the heat
exchanger.
The flanged immersion
heater is faulty.
Replace the flanged im-
mersion heater.
The safety valve drips
when the heating is
switched off.
The valve seat is con-
taminated.
Clean the valve seat.