NOTES
It is important to read, understand and follow all instructions provided with
this product. It is the installer’s responsibility to comply with NFPA 70 &
101, NEC, mounting specifications according to ADA and other applicable
electrical codes.This switch is rated Type NM (Non-Monitored) for non-
emergency signaling. Not to be used in place of panic hardware. To avoid
electrical shock, DO NOT attempt to install this product when power is
on. ADA mounting compliance requires the operable part of the initiating
device shall not be less than 3 1/2 ft. (1.1m ) or greater than 4 1/2 ft. (1.37m)
above finished floor surface. After installation and testing are complete,
provide a copy of this manual to all personnel responsible for testing and
maintenance of this product.
* For access control installations, power for the UB-2PN must be supplied
by a power source Listed to UL294. When used for access control, this
device shall be used as a part of an access controlled egress door system.
It is up to the local AHJ to allow use of this device in place of an automatic
sensor. For higher security installations, lower time limits should be used.
SWITCH RATING
Independent Form “Z” contacts
Rated at: 10A @ 240 VAC
Operating Temp: 15° to 120°F (-9° to 49°C)
1,000,000 Cycles
- 2 -
.91 in.
(23mm)
1.47 in.
(38mm)
2 in.
(51mm)
3.22 in.
(82mm)
4.83 in.
(123mm)
DIE CAST PLATE
SPRING
PUSH BUTTON ACTUATOR
ACTUATOR CAP
2 in. BUTTON
ALIGN TAB ON ACTUATOR
WITH SLOT BUTTON.
TURN CLOCKWISE TO LOCK.
INSERT ASSEMBLY WITH
SPRING INTO PLATE.
REAR VIEW
1
1
2