Position and mount gang plate
to wall. For 2 gang plate, fasten
on 16” (41 cm) centers. For 4
gang plate, fasten on 24” (61 cm)
centers.
Drill a 4” (102 mm) diameter
hole in wall assembly using
existing openings in gang plate
as a guide for each device
required.
Insert outer sleeve in opening and
attach to gang plate. Repeat on
opposing side of wall using inner
sleeve.
Note: When installing NEZ33 the EZ-Path
®
logo needs to be facing you in the
upright position and the arrows should be pointing to the top and bottom of the
device. For vertical installations, horizontal supports should be installed.
For more information on firestop installation, refer to ASTM E3157.