![steute RF RxT SW868-NET-M Mounting And Wiring Instructions Download Page 7](http://html1.mh-extra.com/html/steute/rf-rxt-sw868-net-m/rf-rxt-sw868-net-m_mounting-and-wiring-instructions_1375653007.webp)
Montage- und Anschlussanleitung / sWave.NET Gateway mit Sensor Bridge und Access Point
Mounting and wiring instructions / sWave.NET Gateway with Sensor Bridge and Access Point
//
RF RxT SW868/915/917/922-NET-M
st
eut
e T
chnol
ogies GmbH & Co. K
G
Brück
ens
tr
aße 91, 32584 Löhne, Germany
, www
.s
teut
e.c
om
7 / 16
English
Password settings
To change the admin or api passwords:
- Login as admin user.
- Select the menu »User Settings«.
Fig. 5: User settings
Basic setup
Once the network and login settings are adjusted, the following
steps are required for a minimal system configuration:
- Create a managed group.
- Assign switches to this group.
Please refer to the product website at www.steute.com for a
detailed description.
Troubleshooting
Error
Cause
Solution
Mode LED is off
No power supply or
internal power sup-
ply unit defective
Check power supply,
replace device
Ethernet LED is off
No network cable,
defective network
cable; network
remote station
inactive
Change network
cable; turn on/check
network router or
switch
Configuration
website cannot be
displayed
No network connec-
tion established or
Gateway IP and PC
IP not in the same
subnet
Check network con-
nection (Ethernet
LED) or adjust PC IP
and reset Gateway
to default settings
Access Point re-
ceives no wireless
telegrams
Switch out of
range; antenna not
properly mounted;
wireless receiver
defective
Check distance
to switch; check
antenna; replace
device
Maintenance / Cleaning
We recommend regular maintenance as follows:
1. Remove dirt
Clean enclosure on the outside only. Clean with household cleaning
agents. Do not use compressed air to clean.
Disposal
- Observe national, local and legal regulations concerning disposal.
- Recycle each material separately.
Notices
The electrical connection may only be carried out by authorised per-
sonnel. The wireless receiver must not be used in connection with
devices that may directly or indirectly serve health- or life-saving
purposes or cause hazards by operation to human beings, animals
or asset values.
Subject to technical modifications.
The responsibility taken by the manufacturer of a plant or machine
implies a safeguarding of correct general function. Moreover, steute
does not assume any liability for recommendations made or implied
by this description. From this description new claims for guarantee,
warranty or liability cannot be derived beyond the general terms and
conditions of delivery.