Sterling SDRIOM-2 Installation, Operation And Maintenance Manual Download Page 19

19

D. Belt Tension  and Adjustment

Belt tension is adjusted during the initial run-in and test
periods at the factory. However, the belts are run as slack
as possible to prevent excessive damage to the bearings,
yet tight enough to prevent slippage.

It is necessary, therefore, to check belt tension during the
first few months of operation, and to 

check for proper

tension weekly during the first 60 days,

after which

30-day check intervals are sufficient.

CAUTION: Turn off all power to the equipment
before checking belt tensions.

CAUTION: Do not over tighten belts.

CAUTION: Do not attempt to tighten any belt or
belts by changing the pitch of an adjustable pulley.
This will change the air flow and fan speed.
Consult the factory if the fan speed must be
changed.

Suggested Belt Tension Method

1. Check tension frequently during the first 24-48

hours of run-in operation. Ideal tension is the lowest
tension at which the belt will not slip under peak load
conditions. Over tensioning shortens belt and bearing
life.

2. To properly tension a conventional V-belt drive,use the

following procedure:
a.

Measure the span length.

b.

At the center of the span, apply a force perpendicular
to the span to deflect the belt 1/64 inch for every
inch of span length. For example, for a 40 inch
span, apply a force that will deflect the belt 40/64
or 5/8 of an inch.

c.

Compare the force you have applied with the 
values given in the table below. If the force is
between the values for normal tension and 1 1/2
times normal tension, the belt tension should be
satisfactory. If the belt tension is not within this
range, it can be adjusted by loosening the motor
mounting bolts and adjusting the position of the
motor along its base.

NOTE: A new drive can be tightened to two times
the minimum value shown to allow for normal
drop in tension during the run-in period.

F.

Gaskets

Gaskets are used on doors, inspection covers, some filter
racks, and some outdoor air dampers. Inspect gaskets
periodically and repair or replace as required.

G. Heater

1. At least a yearly inspection is recommended for 

heating installations and more frequently for process 
applications in year-round operation. Your own 
experience is the best guide in determining frequency
of inspection, but as a minimum, the following 
procedure should be followed:
a.

Shut the system down totally, disconnecting or 
locking out power supply so there can be no 
accidental start-up during inspection.

b. Inspect the burner carefully, including upstream and

downstream sides of mixing plates as well as burner
body face. Note that complete burner assembly 
may have to be removed for proper inspection and
cleaning. Any accumulation of scale or foreign 
material on either side of the mixing plates should 
be removed with a wire brush. Check visually that
no holes in the mixing plates are blocked. If any 
burner ports are plugged, even partially, clear them
with a piece of wire. Consult the factory for 
alternate procedures.

If any mixing plates are loose or missing fasteners,
tighten or replace as necessary. Always use zinc
plated or stainless fasteners.

The mixing plates on the burner may display 
“hairline” cracks. These cracks are normal and
caused by thermal stresses occurring during com-
bustion. The presence of these “hairline” cracks in
no significant way affects the combustion efficiency
or performance of the heater. Should a large
opening develop, it may cause difficulties in cross
ignition of flame across the face of the burner. If
this does occur, the specific mixing plate or plates
involved

must

be replaced.

B Section
small 
pulley 
diameter
range in
inches

Belt
Manufacturer &
Type Belt

Pounds
Force for
Normal
Tension

Pounds
Force for
11/2 times
Normal
Tension

3.4-4.2

Gates Hi-Power 

4.4

6.6

Gates Hi-Power 

Gates Hi-Power 

4.9

7.4

5.8

8.7

4.4-4.6

5.8-8.6

WARNING: Do not enlarge burner ports or

performance may be drastically affected.

Note: For recommendation of other types of belts, consult
respective manufacturers.

Summary of Contents for SDRIOM-2

Page 1: ...age injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment WARNING Install operate and maintain unit in accordance with m...

Page 2: ...allow Optional inlet hoods or other large accessories are assembled and shipped mounted and wired whenever possible within limitations of shipping and handling Any optional accessories shipped separa...

Page 3: ...sed to the weather Rotate fan monthly B Locating the Unit Prior to locating the unit authorities having jurisdiction should be consulted before installations are made Approval permits should be checke...

Page 4: ...be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1 2 PSI...

Page 5: ...belts for tightness tension and alignment Do not over tighten belts 6 Check set screws on all bearings pulleys and fans for tightness 7 Check voltage supplied to disconnect switch The maximum voltage...

Page 6: ...using soap solution Unit will run for 5 seconds before ignition trial NOTE 3 OR 4 TRIALS MAY BE NEEDED TO PURGE AIR FROM GAS LINE UnitedTechnologies Electronic Controls Spark Ignitor Watch microammete...

Page 7: ...replaced When checking operation of air pressure switches on systems without pilot the heat switch will have to be turned off approximately five seconds to reset the igni tion control E Temperature C...

Page 8: ...oltage at ignition control C Burner does not light after 5 sec onds pre purge of flame safeguard relay and there is voltage at igni tion control 1 Check power source 2 Check and replace 3 Close or con...

Page 9: ...valves If gas pressure matches unit rating plate and valve does not open replace gas valve or actuator 10 Make sure spark rod is producing a sufficient spark to light off burner make sure porcelain i...

Page 10: ...10 SECTION VII TROUBLESHOOTING P 001004 P 001003...

Page 11: ...d modulating voltages are still not obtained amplifier may be assumed faulty Replace 1 Replace modulator head if not approximately 45 55 ohms for M611Valve and 60 80 ohms for MR212 Valve 2 Clean or re...

Page 12: ...let to modulating valve using a manometer with unit operating at full fire Pressure should be equal to the sum of outlet pres sure setting plus pressure drop of the valve 2 Read manifold pressure usin...

Page 13: ...between amplifier and modulator valve 1 Override Temperature setting is too low 2 Burner capacity may be insufficient 1 Faulty automatic control valve 2 Open wire to automatic valve 13 Symptom Possib...

Page 14: ...inals 4 5 Set T244 or TD244 to max imum setting Measure resistance across wires Meter should read 6000 ohms 1000 T244 If TS244 TD244 are used meter should read 4500 ohms 1000 TS244 and 2100 ohms 150 T...

Page 15: ...cessary 1 Move TS144 to location where average temperature can be sensed 2 If proper temperatures are not observed refer to Discharge Air Temperature calibration procedures 1 Clean replace valve and o...

Page 16: ...h pressure regulator to match the appliance rating a Remove the pressure regulator adjustment cap b Using a screwdriver turn the inner adjustment screw for HI pressure clockwise to increase or counter...

Page 17: ...sure that no com bustible or hazardous material has been stored within the clearances as shown on the unit name plate 3 Quarterly a Complete the monthly maintenance schedule b Check the belt tension f...

Page 18: ...casing of the motor Add a small amount of a clean good grade ball bearing grease such as Exxon Polyrex EM or equal with a low pressure grease gun Run the motor five minutes before removing the grease...

Page 19: ...inspection covers some filter racks and some outdoor air dampers Inspect gaskets periodically and repair or replace as required G Heater 1 At least a yearly inspection is recommended for heating insta...

Page 20: ...e solution 5 Inspect the support means to be sure that everything is firmly anchored in place SECTION IX MAXON NP I AIRLO BURNERS Inspection and Maintenance of Gas Ports Conduct initial inspection wit...

Page 21: ...ontinuous low fire 2 Remove cap B and loosen lock screw C Turn D to desired low fire adjustment Clockwise rotation reduces minimum flow rate 3 Tighten screw C replace cap B and reconnect wire to ampli...

Page 22: ...m can be isolated to the electronics and this may once again be reviewed in the check list After test remove the test resistor and reconnect the Discharge Air Sensor to terminals 3 and 4 If Remote Tem...

Page 23: ...lem is identified with the space temperature sensing and or temperature selecting components and circuits See Troubleshooting Guide If proper delivered air temperatures are not observed check calibrat...

Page 24: ...cient ventilation air which results in inadequate dilution of combustion products gen erated by the heater may create hazardous concentrations of carbon monoxide nitrogen dioxide and other combus tion...

Reviews: