2-40 HP Portable Chillers
Chapter 2: Functional Description
16 of 70
Figure 1: Optional Pump Amperages
Voltage
Construction
HP
Full Load Amps
Bronze Turbine
.75
5.4
1 6.4
1.5 7.5
2 9.6
208-230/1/60
SS
3 12.7
Bronze Turbine
.75
1.5
1 1.8
1.5 2.3
2 3.1
3 4.2
5 6.2
7.5 9.8
10 13.2
SS
15 19.0
2 2.7
3 4.5
5 6.6
460/3/60
Dual SS
7.5 9.0