background image

 

Start-up 

1. Prestart: 

Check for correct dry cooler fan rotation. This can be done 
by quickly jogging the fan contactor. Be sure that the fans 
run freely. The same check is recommended for pumps. 

2.  Filling and Purging the System 

The system should be pressure tested before adding glycol. 
The system can be tested with air or water, however if the 
ambient temperature is at or below freezing the use of air 
is recommended. Test pressure should not exceed 60 
PSIG. 

a. 

Roof Mounted Fluid Cooler 

To fill the system, pour the premixed water and glycol 
into the expansion tank. Fill the system until the 
expansion tank is half full, then purge the air from 
ALL vents. Operate the system for a minute, then 
purge ALL vents again, and add glycol as required. 
Repeat the purging of all vents after the first hour of 
operation and again after several hours of operation. 

b. 

Ground Mounted Fluid Cooler 

The fluid cooler may be lowest point in the system, 
consequently the premixed water and glycol will have 
to be pumped into the system. Close the shut off valve 
and open the two hose bibbs installed in the piping 
run on the leaving side of the pump, see piping 
diagram. 

Connect a pump and hose to the hose bibb away 
from the pump and a hose to the hose bibb closest 
to the pump. Begin pumping the glycol mixture into 
the system at FULL PRESSURE. For the return 
hose you should close the hose bibb so that you 
get only a small flow of fluid or air. This is 
necessary so you will build a head of fluid which will 
force the air from the system. Once all the air is out 
you will have a steady flow of only fluid. At this joint 
you should close off the two hose bibbs and open 
the shut off valve. See Diagram 3. 

3. 

Flow Adjustment Procedure: 

Once the system is completely full of fluid, start the fluid 
circulating pump. To assure proper fluid flow, adjust the 
shut-off valve for required GPM by checking pump curve 
and observing gauge pressure, or by using an in-line flow 
meter. 

4. Instruction 

Envelope: 

Keep wiring diagrams, instructions, list of spare parts, in 
an envelope within easy reach of the installed dry cooler. 

Diagram 3. 

 

Space and Location Requirements 

The most important consideration which must be taken 

into account when deciding upon the location of air-cooled 
equipment is the provision for a supply of ambient air to the 
condenser, and removal of heated air from the fluid cooler 
area. Where this essential requirement is not adhered to, it 
will result in higher head pressures, which cause poor operation 
and possible eventual failure of equipment. Units must not be 
located in the vicinity of steam, hot air or fume exhausts. 

Another consideration which must be taken is that the 

unit should be mounted away from noise sensitive spaces 
and must have adequate support to avoid vibration and noise 
transmission into the building. Units should be mounted over 
corridors, utility areas, rest rooms and other auxiliary areas 
where high levels of sound are not an important factor. Sound 
and structural consultants should be retained for 
recommendations. 

 

Summary of Contents for 25001301

Page 1: ... Installation 2 Rigging Instructions 3 Internal Volume and Weight 4 Electrical Wiring 4 6 System Installation Piping Installation Glycol Charge 7 Mixing Glycol and Water Glycol Sludge Prevention Fluid Circulating Pump 8 Start up Space and Location Requirements 9 10 Typical Piping In Warranty Return Material Procedure 11 Replacement Parts 12 ...

Page 2: ...is recommended The roof must be strong enough to support the weight of the unit Concrete slabs used for unit mounting should be installed level and be properly supported to prevent settling A one piece concrete slab with footings extending below the frost line is recommended The dry cooler should be located far enough away from any wall or other obstruction to provide sufficient clearance for air ...

Page 3: ...acent units Sufficient free area should be left around and below unit to avoid air restriction to coil Vertical airflow type units should be located no closer than the width of the unit from a wall or other obstruction It two or more units are to be positioned in the same area a 3 ...

Page 4: ...iagrams shown are only basic and do not show fuses disconnect switches etc which must be provided in the field All standard motors have internal inherent overload protectors Therefore contactors can be used instead of starters requiring thermal protectors eliminating the problem of furnishing the proper heating elements All dry coolers or units are furnished with either single phase or three phase...

Page 5: ...5 Double Row of Fans Single Row of Fans Diagram 1 Typical Fluid Cooler Wiring Diagram Without Fan Cycle Controls ...

Page 6: ...Double Row of Fans Single Row of Fans Diagram 2 Typical Fluid Cooler Wiring Diagram With Standard Fan Cycle Controls 6 ...

Page 7: ...ture Any refill should be controlled so as to main tain the proper glycol to water ratio Table 3 shows pressure drops for various pipe sizes at flow rates commonly used with a typical dry cooler These pipe sizes are not necessarily always correct for the run from the condenser to the dry cooler Proper pipe size will depend on available pump head This can be determined by subtract ing from the tota...

Page 8: ...ate inhibitor treatment must be used 4 The glycol manufacturer should provide inhibitor check service and supply additional inhibitor as required Fluid Circulating Pump Mechanical seal type pumps must be used for glycol systems Gland type pumps would cause glycol waste and if used with a pressure reducing valve will lead to dilution of the glycol mixture and eventual freeze up Pump is selected for...

Page 9: ...uid or air This is necessary so you will build a head of fluid which will force the air from the system Once all the air is out you will have a steady flow of only fluid At this joint you should close off the two hose bibbs and open the shut off valve See Diagram 3 3 Flow Adjustment Procedure Once the system is completely full of fluid start the fluid circulating pump To assure proper fluid flow a...

Page 10: ...its placed side by side the minimum distance between units is the width of the largest unit If units are placed end to end the minimum distance between units is 4 feet Multiple Units room is left for maintenance work through access doors and panels Overhead obstructions are not permitted When the unit is in an area where it is enclosed by three walls the unit must be installed as indicated for uni...

Page 11: ...lude part number model number and serial number of the unit involved Material may not be returned except by permission of authorized factory service personnel of Sterling Inc in New Berlin Wisconsin A Return Goods tag will be sent to be included with the returned material Enter the required information on the tag in order to expedite handling at our factories and prompt issuance of credits All par...

Page 12: ...Sterling Inc 2900 S 160th Street New Berlin WI 53151 262 641 8610 y Fax 262 641 8653 www sterlco com ...

Reviews: