Sterling Power Products DAI-1500C-12 Series User Manual Download Page 25

-2

2

L. Programming Aux Contacts (AUX1, AUX2) 

   

L.1.1 Principle 

  The Auxiliary unit  can be basically programmed for any operating situation of   

the unit    which is indicated with a LED. The programming is possible for one or   
more operating situations. If the contact is programmed for many situations, it is   
activated as soon as the unit    finds itself in any one of the programmed   
situations. 
 

L.1.2 Example 

   

L.1.2.1 Auxiliary contact as generator starter 

    When in the programming of the Auxiliary Contact, the State of Charge (SOC)   

LED`s (LED 8) can be used as a condition, then you must take note of the   
following requirements. 
If you have to start an emergency back-up supply with a battery having a certain   
SOC, then two SOC levels must be programmed. The first (i.e. Battery 25% LED) 
for the starting or activating the Auxiliary Contact and the second (i.e. Battery   
100% LED ) for stopping or deactivating the Auxiliary Contact. By programming   
in this way the Auxiliary Contact starts with the lowest set condition and stops   
when it has reached the highest programmed condition through charging. 
 

L.1.2.2 Auxiliary Contact as Twilight Switch (With solar charger option) 

The Auxiliary Contact    can also be used as a twilight switch , i.e. for   
automatically operating exterior lighting. Solar modules connected to the unit   
will measure the light intensity. If the unit    is operating without solar modules   
and a twilight-switching function is desired, you can connect small solar cells with   
the nominal voltage of the unit to the SOLAR terminals for the purpose of   
measuring the light intensity. To function as a twilight-switch the Auxiliary Contact   
must be programmed so that the condition “SOLAR CHARGE” LED is active.   
Programming must be carried out in steps and in accordance with the description   
for the programming of the Auxiliary Contact. 

 
L.1.3.3 Manual operating of Auxiliary Contact:

 

The Auxiliary Contact can be operated manually at any time by pressing the   
“AUX” button. The “Multi-display show 

  (

) to indicate that the   

Contact is manually operated. By pushing the “AUX CONTACT” button again ,the   
Contact is deactivated. Multi-display show 

  (

). By pushing it a third time,   

automatic functions are restored and Multi-display show 

  (

). 

Summary of Contents for DAI-1500C-12 Series

Page 1: ...BINED PURE SINE WAVE INVERTER UPS BATTERY CHARGER SOLAR SHORE USER MANUAL Sterling Power Products England Tel 01905 453999 Fax 01905 458836 www sterling power com help sterling power com STERLING POWE...

Page 2: ...2 C Introduction 4 D Installation 8 E Operation 11 F Disabling Functions 17 G Charger Information 19 H n a I Auxiliary Contacts 21 J The Remote control unit 21 K n a L Programming Aux Contacts AUX1 AU...

Page 3: ...tion 2 High surge capacity and soft start design for heavy inductive loads such as air conditioning Load detection system for power saving mode Extremely high efficiency Battery Charger The 3 in 1 ser...

Page 4: ...3000C 12xx DAI 1500C 24xx DAI 1500C 24xx Temperature BTS A 15 m Remote controller RCC A 03 3m RCC A 15 15m Any personnel who install the unit and or works with it must be fully familiar with the cont...

Page 5: ...consumer rights under local trade practices act This warranty does not extend to products which have been opened altered or repaired by persons other than authorized by Sterling or to products which b...

Page 6: ...through carelessness Never charge frozen batteries This unit is not to be used or sold for life support equipment or applications B 1 Special Precautions While working on batteries there should always...

Page 7: ...inal power of the Combi The inverter is protected against overload and short circuit A power stage with the latest MOS FET power transistors a toroidal transformer and a fast regulating system make up...

Page 8: ...that the batteries are charged correctly With the unit batteries can be charged with a generator and with the solar modules at the same time The charging of batteries with both energy sources is carri...

Page 9: ...6 C 2 1 Parallel Connection C 2 2 Series Connection...

Page 10: ...7 C 2 3 Parallel Series Connection...

Page 11: ...ombi is designed in such a way that it will work most efficiently when mounted vertically In mobile installation it is important to keep vibrations to a minimum D 2 Rear Panel Connections A Battery Ba...

Page 12: ...it to charge the capacitors This is another reason to install a battery fuse circuit breaker For this reason follow strictly the safety measures described in this manual DO NOT INSERT THE BATTERY FUSE...

Page 13: ...D 3 5 Connection to Aux1 AUX2 On these three terminals is a potential free change over contact capable of switching a maximum current and voltage of 16A 250V ac The multi display on the front of Combi...

Page 14: ...10 PB3 PB2 11 2 1 3 4 E 2 Push buttons Push buttons Name Description PB1 RUN STOP RUN STOP key PB2 FUNC k Operation mode select key PB3 AUX1 Auxiliary contract aux1 aux2 Manual Active change And Funct...

Page 15: ...ect or 2 Day or Night cloudy day 4 SOLAR CHARGER Solar charger is working Solar charger is disabled 5 AC OUT There is voltage at the AC OUT terminal No voltage at the AC OUT terminal 6 INVERTER Green...

Page 16: ...onitor 9 6 Indicator of error message 12 POWER MONITOR Displays the value of the output power in of max continuous power in Inverter Mode and the charge current in Amps in Charger Mode In this mode th...

Page 17: ...change For example if you wish to switch the power saver function off you find that the power saver function is attached to function 2 and that selection means off To select this desired option go to...

Page 18: ...Overload If the unit is overloaded for too long or too heavily it switches off The Multi display will show and the RUN STOP LED will RED Blink After approximately 10 seconds the Inverter switches on a...

Page 19: ...ns to 12 1V resp 24 2V the inverter switches ON automatically One minute before the Inverter switches OFF due to low voltage a buzzer will be heard The low voltage is set to 11 8V resp 23 6V These set...

Page 20: ...ilities shown in the following diagram In programming mode the display only shows the different types of program with the Charger Transfer and Inverter functions To change the type of programming pres...

Page 21: ...ed This is factory setting The inverter ins disabled Only the Bypass switch and charger will work normally Charger and Bypass switch are disabled The inverter will work continuously even if there is a...

Page 22: ...y the AC load the less power is given to the charger Priority for the AC Loads When power sharing is used the red 200 LED on the power monitor is lit to show that the battery charging is being limited...

Page 23: ...m the grid or a generator the voltage and quality of the power running the AC load will be the same as that coming from the grid or generator The unit cannot modify the incoming AC supply G 3 The sola...

Page 24: ...e control unit As an option a Remote control unit can be connected to the unit All operating controls and displays are available on the Remote control unit The Remote control is supplied with a 3m lon...

Page 25: ...d stops when it has reached the highest programmed condition through charging L 1 2 2 Auxiliary Contact as Twilight Switch With solar charger option The Auxiliary Contact can also be used as a twiligh...

Page 26: ...stem Thoroughly clean and check all battery connections within the battery bank and to the unit Ensure all connections to the unit are tight Ensure the vents at the top and bottom of the unit are clea...

Page 27: ...ltage 265 Vac 350 V peak Minimum input voltage Adjustable 150 230Vac Input Frequency range 45 63Hz Charging current adjustable 0 50A 0 35A 100A 0 70A Setting of AC INPUT current POWER SHARING 0 to 15A...

Reviews: