5.0   TROUBLESHOOTING

6.0   ILLUSTRATIONS

3

ITEM

5.1 

SYMPTOM

Emitter™ Does Not Light

RECOMMENDED ACTION

(in order of priority)

1. Ensure that fixture cover is affixed to base and that it trips the interlock switch.
2. Ensure that on/off switch is set to 

on

.

3. Turn off power for 10 seconds, and then turn power back on.
4. Replace Emitter with known working Emitter. Normal replacements recommended 

once per year.

5. Check line voltage.
6. Check wiring to Emitter.
7. Replace power supply.

5.2 

Low Output (Radiometer Reading)
or Visibly Weak Light

1. Replace Emitter with known working Emitter.
2. Check line voltage.
3. Check wiring to Emitter.

5.3 Red/Orange 

Light

1. Check ambient temperature. If the temperature is at or below 35°F, Emitter is too 

cold to operate properly.

2. If ambient temperature is in excess of 35°F, follow actions for the 

Low Output symptom.

2"

9.00

9"

16", 20", 24", 30", 36", 42"

1/2" CONDUIT INLET    

4.3

END VIEW

OFF/ON SWITCH

BLACK

  WHITE

INTERLOCK SWITCH

3.1

2.0

4.3

BLACK

WHITE

INTERLOCK

SWITCH

LIGHTED ON/OFF

SWITCH

ELECTRONIC BALLAST

BLUE END

120 THRU 277 V

50 / 60 HZ

EMITTER

Summary of Contents for SE Series

Page 1: ... General 2 0 Installation 3 0 Operation Maintenance 4 0 Trouble Shooting 5 0 Illustrations 6 0 Spare or Replacement Parts 7 0 1 0 SAFETY CONSIDERATIONS TABLE OF CONTENTS MODEL SE SERIES 120 277 Vac Patents 5 334 347 5 817 276 5 866 076 6 245 293 6 267 924 6 280 686 6 313 470 6 372 186 6 423 882 6 500 267 6 589 476 6 627 000 INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS Improper installation ...

Page 2: ... Wrap suspect items with aluminum tape use metallic conduit or use other appropriate shielding where these items may be in line of sight of UVC 3 4 Determine the most desirable location for the intended use and install reflecting material CAUTION Do not drill into coil Freon lines or other mechanical equipment 3 5 Using the fixture base as a template scribe and then create one insertion hole 1 dia...

Page 3: ...wiring to Emitter 7 Replace power supply 5 2 Low Output Radiometer Reading or Visibly Weak Light 1 Replace Emitter with known working Emitter 2 Check line voltage 3 Check wiring to Emitter 5 3 Red Orange Light 1 Check ambient temperature If the temperature is at or below 35 F Emitter is too cold to operate properly 2 If ambient temperature is in excess of 35 F follow actions for the Low Output sym...

Page 4: ...he 1 UVC for HVAC product sold worldwide Please contact your local supplier or Steril Aire directly if we can provide any further information or service Your satisfaction is very important to us Please call 1 800 2 STERIL 783745 or log onto www steril aire com Steril Aire Inc cannot and does not guarantee that all organisms will be inactivated or killed or that use of Steril Aire Inc UVC Emitters ...

Reviews: