5.0 TROUBLESHOOTING
3
6.0 ILLUSTRATIONS
2"
"A" CTS
16, 20 OR 24"
"B"
1" DIA HOLES ON "A" CTS
REQUIRED TO INSTALL
FIXTURE MAY BE INSTALLED
IN ANY ORIENTATION
4.3"
3.0
INTERLOCK
LIGHTED ON/OFF SWITCH
WIRE OR CONDUIT INLET
TWO
WHITE
USE BOTH
BLACK
RSE 2-10 RSE 2-14
A
10"
14"
B
13"
17"
BLACK
2 WHITE
INTERLOCK
SWITCH
OFF / ON
SWITCH
ELECTRONIC BALLAST
EMITTERS
115 THRU 230 VOLT
50/ 60 HZ
WHITE
END
115 THRU 230 V
50 /60 HZ
AIR FLOW
COOLING COIL
AIR FLOW
AIR
FLOW
ITEM
5.1
SYMPTOM
Emitter™ Does Not Light
RECOMMENDED ACTION
1. Ensure that fixture cover is affixed to base and that it trips the interlock switch.
2. Ensure that on/off switch is set to
on
.
3. Turn off power for 10 minutes, and then turn power back on.
4. Replace Emitter with new unit. Normal replacements recommended once per year.
5. Check line voltage.
6. Check wiring to Emitter.
7. Replace power supply.
5.2
Low Output (Radiometer Reading)
or Visibly Weak Light
1. Replace Emitter with new unit.
2. Check line voltage.
3. Check wiring to Emitter.
5.3 Red/Orange
Light
1. Check ambient temperature. If the temperature is at or below 35°F, Emitter is too
cold to operate properly.
2. If ambient temperature is in excess of 35°F, follow actions for the
Low Output symptom.
seconds
1. Ensure that fixture cover is affixed to base and that it trips the interlock switch.
2. Ensure that on/off switch is set to on.
3. Turn off power for 10 seconds, and then turn power back on.
4. Replace Emitter with known working Emitter. Normal replacements recommended
once per year.
5. Check line voltage.
6. Check wiring to Emitter.
7. Replace power supply.
with known working Emitter.