Adjustment of the detection zone/reach
The shrouds supplied can be
used for deliberate adjustment
of the detection zone. Using
these, it is possible for exam-
ple to cleanly separate individ-
ual workplace areas in an
open-plan office so that only
movements in the area of the
respective desk group are de-
tected. We recommend acti-
vating test mode for rapid and
precise adjustment of the de-
tection zone (see page 16).
1
2
3
4
5
6
7
8
Vertical separation =
reduction of the angle of coverage
Horizontal separation =
reduction of the reach
The shrouds are divided into 8 areas (horizon-
tally). The reach is reduced depending on the
shrouds applied (number of areas).
0
(without cov.)
= 12 m
= 12 m
1
= 6.5 m
= 10 m
2
=
5 m
=
9 m
3
= 3.5 m
=
8 m
4
=
3 m
=
6 m
5
= 2.3 m
= 4.5 m
6
= 1.5 m
=
3 m
7
=
1 m
= 2.2 m
8
< 0.5 m
<
1 m
19
BLS DIMM
IR remote control
For the sensor BLS DF the op-
tion also exists of adjusting
the desired light level by
means of an infrared remote
control. The last selected set-
ting is respectively maintained
in this case. By constantly
pressing the (–)-button, the
lighting also be switched OFF
completely using the remote
control. By subsequent press-
ing the (+) button, the desired
level of brightness can be
readjusted.
Reset function
By simultaneously pressing
both buttons (+) and (–), all the
modifications made using the
remote control are reset to the
brightness setting adjusted on
the sensor.
Important note:
During adjustment of the
brightness setting, it should
be noted that the measured
brightness values of the sen-
sor refer to the installation site
of the sensor under the ceiling
and may therefore not neces-
sarily correspond to the
desired brightness at the
workplace.
Guideline values for adjusting the lux and time value
The following guideline values may be taken as a basis:
Brightness setting:
Passageways (not working areas):
200 lux
Working areas (offices, training rooms, workshops etc.):
500 lux
Working areas requiring good light:
(technical drawing, laboratories, precise work)
700 – 1000 lux
Switch-off delay:
The switch-off delay can be continuously adjusted according to the use of the respective rooms:
Mainly standing activities (e. g. photocopier room, passageways etc.):
4 min.
Mainly seated activities (desk work by 3–4 individuals):
7 min.
Mainly seated activities (desk work by 1–2 individuals):
10 min.
Seated activities with little movement (reading, EDP, etc.):
> 10 min.
If the lighting immediately switches ON again in response to movement in spite of occupancy,
the switch-off delay is to be increased.
18
Functions
BLS DF
A
r
Shroud
(see drawing)
Reach
(installation
at a height
of 2.5 m)
Reach
(installation
at a height
of 5 m)
AC
SE
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 20