Setup and Commissioning
Test mode
Ř
Ensure that the sensor is in test
mode.
- set time delay to minimum
setting of 5 seconds
- set light level to maximum
(“day” setting, light level
function overridden - factory
setting)
Ř
Turn power ON at the circuit
breaker (lights will turn ON).
After a warm up period of up to
one minute, lights will turn OFF
if the sensor does not detect
motion.
12
IS 3360-24
IS 345-24
IS 3180-24
Ř
Walk in view of sensor, lights
should turn ON. Be still for 5
seconds and lights will turn
OFF.
Important: Only select time and
light level setting with the lens in
place.
Light level
The light level feature allows
lighting to remain OFF
during daylight, regardless of
occupancy. Daytime operation
is at 200 footcandles (factory
setting). Nighttime operation is at
.2 footcandles.
.2-200 fc