22
23
Dimensions (H
x
W
x
D)
Surface-mounted installation, round Ø
126
×
52 mm
Surface-mounted installation, square 95
×
95
×
52 mm
Concealed installation, round Ø
124
×
64 mm
Concealed installation, square
94
×
94
×
64 mm
Application
inside buildings
Power supply
KNX bus voltage, 21 V - 30 V
(SELV)
Sensor system
5.8 GHz high frequency
Mounting height
2-2.8 m
Transmitter power
approx. 1 mW
Settings
via ETS software, remote control or BUS
Angle of coverage
360° with 180° angle of aperture
Basic brightness
1-255 min
Twilight setting
2-1000 lux, teach
(only via RC6 or Smart Remote)
Twilight setting,
basic brightness
2-1000 lux, teach
(only via RC6 or Smart Remote)
Light output
Light 1 – Light 2
Switching / dimming / basic brightness
Lighting stay-ON time
1-255 min
HVAC stay-ON time
1-255 min
HVAC switch-ON delay
Room surveillance, 1-255 min
Further outputs
Sabotage protection
IP rating
Surface-mounted: IP54
Concealed: IP20
Temperature range
-20°C to +50°C
9� Technical specifications
Malfunction
Cause
Remedy
No power at the sensor
n
Break in wiring
n
Check KNX power
supply
Sensor will not switch ON
n
Bulb faulty
n
Twilight setting set
to night-time mode
during daytime
operation
n
Change bulb
n
Adjust setting
Sensor will not switch OFF
n
Continuous movement
in the detection zone
n
Check zone
Sensor keeps switching
ON/OFF
n
Curtains, plant etc.
moving in the sensor's
detection zone causing
the sensor to respond
n
Check zone
10� Troubleshooting