Optional Auto
Drain Valve
Model AD-900
Water Inlet
⅜" Compression
Fitting
¾" Safety
Relief Valve
¾" Steam
Outlet
Knockouts for
Electrical Supply Line
Knockouts for
Control Cable
04/18
Pub. No. 231-B
- 1 -
Install Upright
and Level
C
US
®
IMPORTANT:
The warranty of this product is voided if it is used in a commercial application or for anything other than a residential
steambath installation. All electrical connections must be performed by a licensed electrician in accordance with Local and National
Electric Codes.
Electrical Installation Instructions
Steambath Generators
Models: SMP-12 and SMP-15
NOTE:
A “
TSC
”
series control is required to operate the "SMC"
generator.
The Steamist “SMP” Generator operates with only “TSC” series
controls mounted inside and an optional TSX control located
outside the steamroom. It’s small enough in size to be tucked
away using very little space in a vanity, closet, or basement, but
large enough to provide steam for most residential baths.
The Steamist “SMP” Steambath Generator comes factory
assembled, carefully wired and tested.
1.
Pre-Installation
a) Proper electrical supply (208 or 240 Volt): See rating
label on Steam Generator and Chart on page 4.
Determine proper size of wire, voltage, amperage, and
phase for the Steam Generator. 90°C copper wire is
required for generator connection.
b) In-line fuse/circuit breaker required: Fuse/circuit breaker
to be installed must be sized in accordance with chart
on back page. Do NOT install a GFI (Ground Fault
Interrupter) to this equipment (per article 210-8 in the
National Electric Code).
c) Route power supply cable to the location where the
Steam Generator will be installed (before walls are
closed).
2.
Electrical Rough-in
a) Route appropriate power cable to the location the Steam
Generator will be installed. If receptacle is desired,
mount the box for the receptacle near the location of
the Steam Generator.
NOTE:
The plug and receptacle require a rating of no
less than 250V and proper amperage. Refer to chart on
page 4 for amperage rating.
After the walls are complete, the Steam Generator and
Control can be wired.
3.
Steam Generator Electrical Installation
WARNING:
All power to the Steam Generator must be
turned off.
a) Remove the two screws holding the electrical access
cover and remove cover.
b) Locate the supply line knockout. Mount proper strain
relief into knockout hole.
c) Strip back power cable’s outer insulation jacket
eight inches and insert into Steam Generator.
Strip back insulation ½" from the three (3) incom
-
ing wires (two power and one ground).
d) Insert ground wire into grounding lug located
on the right side of the electrical compartment
and secure.
CAUTION:
Be sure the ground wire does not
come in contact with a live electrical part.
e)
Locate the terminal/fuse block in the upper portion
of the electrical compartment. Insert power wires
into the power lugs on the front of the terminal/fuse
block and secure.
4.
Optional Auto Drain Valve Connection
a) Open knockout for Auto Drain Valve conduit
connection.
b) Route flexible conduit from valve to knockout and
secure.
c) Connect two wires from valve to the auto DRAIN
connection J11 on the printed circuit board (see
Figure 2).
Figure 1 - Steam Generator
Important:
Locate Publication No. 199 “Steam Bath Important Safety Instructions”. This publication includes a Warning
label that the contractor must install on the wall near the entrance to the steam room in a highly visible location. This
label and its additional safety information are packaged with the generator in the envelope containing the installation
instructions. If it is lost or missing contact Steamist (201-933-0700) for a replacement Publication No. 199. This publica
-
tion along with all documents must be left with the owner.
!
®