Modular Jack

Protective

Covering

(Remove)

Multi-Conductor

Control Cable

(25 feet)

Black Plastic

Strain Relief

Clamp

Ground

Connection

Electrical

Supply Wire

208/240V

L1 & L2 Power

Connections

Steam Outlet

Safety Valve

Optional Steamist

Splitter for Two

Controls

Plug 

Electrical Installation Instructions

Checklist

Models: SM-46 and SM-79

Figure 2 - Internal Electrical Connections

03/09

Pub. No. 217-J

- 2 -

Before starting, insure that the conditions of the following checklist have been met:

The proper size Steam Generator has been selected by 
using the sizing page in the “Full Line Brochure,” “Pricing 
Guide,” or “The Generator Sizing Guide” in the Residen-
tial Systems/Steambath Product Information section of 
the Steamist website - www.steamist.com.

CAUTION: An improperly sized Steam Generator will 
NOT produce the amount of steam necessary to reach 
selected temperature.

The proper voltage Steam Generator has been selected 
(i.e., 208V or 240V). A 208V Generator operating on 
240V will damage the heating element, and a 240V 
Generator operating on 208V will result in a 25% 
loss of power.

The Steam Generator is installed in an upright position.

The proper sized 90°C wire and circuit breaker have 
been used.

The circuit breaker is NOT a GFI (Ground Fault 
Interrupter) type.

The Steam Generator is properly grounded.

The circuit breaker or disconnect switch is on.

Water supply is open to the Steam Generator.