D2569_01_01 CN5192 CS2017_User_Guide
IMPORTANT - CE & SAFETY REQUIREMENTS
Product must be mounted, inside a suitable enclosure providing environmental protection to IP65 or greater.
To maintain CE EMC requirements , input wires must be less than 3 metres.
The product contains no serviceable parts , or internal adjustments. no attempt must be made to repair this product. Faulty units must be returned to supplier for repair.
This product must be installed by a qualified person. All electrical wiring must be carried out in accordance with the appropriate regulations for the place of installation.
Before attempting any electrical connection work, please ensure all supplies are switched off.
ABSOLUTE MAXIMUM CONDITIONS ( To exceed may cause damage to the unit) :-
Supply Voltage
± 30 V dc (Protected for over voltage and reverse connection)
Current with over voltage
± 100 mA
Input Voltage
± 3 V between any terminals
Ambient
Temperature
(-40 to 85) °C Humidity (10 to 95) % RH (Non condensing)
USER GUIDE
SMART PCB TRANSMITTER INPUT PT100
TWO WIRE (4 to 20) mA
Every effort has been taken to ensure the accuracy of this document, however we do not accept responsibility for damage, injury, loss or expense resulting from errors and omissions, and we reserve the right of amendment without notice.
Important - Please read this document before any installing.
PRODUCT
SPECIFICATION
RECEIVE
AND
UNPACKING
CONFIGURATION
Please
refer
to
the
product
data
sheet
for
full
specification.
Please
inspect
the
packaging
and
instrument
thoroughly
for
any
signs
of
transit
damage.
If
the
instrument
has
been
damaged,
please
notify
your
supplier
immediately.
The following parameter can be configured by simply entering as prompted by the software package.
· Low range
· High range
· Units (°C, °F)
· Burnout (direction of output current on sensor burnout)
Factory
default:
Low
Range
=
0
High
Range
=
100
Units
=
°C
Burnout
=
UPSCALE
Input PT100
1
2
3
2 Wire (4 to 20) mA
Output
PT100
+
-
V
s
Loop
Load
+
-
IMPORTANT
Do
not
attempt
to
configure
the
Transmitter
when
connected
to
a
loop
supply.
COMMS
Pt 100
USB SPEEDLINK SOFTWARE
COMPUTER
USB CABLE
USB CONFIG-UNIT
Red
+
Black
‐
CONFIGURATOR