STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD4 Gas Detector
TD19/001
Issue:
5
Change Note:
1869
Page 21
7.4.6.
E : 8
– Factory restore
The FGD4 can be restored to the default factory settings.
•
Press MENU to open the menu system.
•
The sensor type will be displayed.
•
Press
to store the new value.
Note: Pressing the MENU button rather than the
button
exits without any change.
•
Press MENU to close the menu system.
Note:
This option will restore the sensor to the factory default values. The user
must set all parameters before using the unit
7.4.7.
E : 9
– Engineer diagnostics
This feature is a view-only feature. No configuration changes are possible
from within this menu.
The information is for use of Status Scientific Controls personnel.
•
From the menu system select menu option:
E: 9
and press
.
•
Using the
or
buttons, display the required setting. The
displayed values are as follows:
E : 90
Reading
E : 91
Current sensor temperature °C
E : 92
Sensor AtoD counts
E : 96
Status flags