STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10A Oxygen / Toxic Gas Detector
TD18/002
Issue:
16
Change Note:
1904
Page 23
E : 47
– Set the Dac analogue output FSD
4.8.1.
E : 1
– Sensor Zero
Refer to section 5.1.1. for sensor calibration details.
4.8.2.
E : 2
– Sensor Span
Refer to section 5.1.2. for sensor calibration details.
4.8.3.
E : 3
– Sensor FSD
The sensor measuring range is set by this menu.
•
From the menu system select menu option:
E: 3
and press
ENTER.
•
Using the INCrease and DECrease buttons, select the required
value.
•
Press ENTER.
Note: Pressing MENU instead of ENTER will exit the menu
without changing the value.
•
Press MENU to close the menu system.
Note:
changing the FSD must be used with caution. The setting must be
within the capability of the sensor.
4.8.4.
E : 4
– Output Zero (4mA)
Refer to section 5.2.1. for output calibration details.
4.8.5.
E : 5
– Output Span (20mA)
Refer to section 5.2.2. for output calibration details.