STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10A Oxygen / Toxic Gas Detector
TD18/002
Issue:
16
Change Note:
1904
Page 32
4.8.21. E : 47
– Analogue Output FSD
This menu option allows the full-scale gas level to be selected that relates to
the 4 to 20 mA output.
•
From the menu system select menu option:
E: 47
and press
ENTER.
•
Using the INCREASE and DECREASE buttons; adjust the FSD
to the required level.
•
Press ENTER, ‘- - - - ‘will be displayed to indicate that the new
setting has been accepted.
Note: Pressing MENU instead of ENTER will exit the menu
without changing the FSD.
•
Press MENU to close the menu system.