background image

D2598-01-01 CN5370 USBTTX CONFIG User Guide

4.0 OPERATION

5.0 SPECIAL CONDITIONS FOR USE

4.1  To use your USB configuration equipment you will first need to install USB Speedlink software, which is available as a free 
download from 

http://www.status.co.uk/software.html

 . You will also need a Status Instruments USB-CONFIG-MKII configuration 

module.

4.2  Connect the USB-CONFIG-MKII module to a Windows computer using the integaral USB lead, connect the USB-CONFIG-MKII 
module to the USBTTX ATEX unit with the jack plug and socket connection.

4.3 Use either the crocodile clips or the ferrule conectors to attach the USBTTX module via its jack plug connection to the (4 to 20) mA 
loop connection pins on the TTR200X, TTC200X, SEM1801XR, SEM1802XR, SEM1801XTC or SEM1802XTC.                                                                                                                             

4.4  Connect the unit you wish to configure to the USBTTX module via the appropriate leads, refer to the instruments user guide for 
the connection details.

4.5  The software will recognise when the USB-CONFIG-MKII module is attached. This may take a few minutes the first time the USB-
CONFIG-MKII Module is attached while the software drivers are loaded.  

4.6  In the USB Speedlink software select the type of instrument to be configured, the USB equipment will now communicate with the 
instrument and present the correct screen for configuring the instrument.

4.7 Note:- For SEM1802XR and SEM1802XTC each channel will need to be connected to and configured individualy. 

5.1  The USBTTX  is only to be connected to a Windows personal computer or Windows laptop type computer via a Status Instruments 
USB-CONFIG-MKII module

5.2  The USBTTX with USB-CONFIG-MKII and connected computer are only to be used in the safe area

6.0 MARKING

7.0 GENERAL INFORMATION

7.1  The ATEX USBTTX module is powered completely from the USB port on your computer via the Status Instruments USB-CONFIG-
MKII; you do not require an external power supply for configuration. The USBTTX module will power the instrument connected to it 
during the configuration process for configuration and can also take live readings and perform certain adjustments. 

It is not recommended to leave the module plugged into a laptop computer for long periods of time when the laptop is running on 
batteries as this will affect battery life adversely, especially if an instrument is left connected to the configurator.

7.2  If you have any questions regarding the configuration of Status Instruments equipment please contact your supplier.

7.3  Please see the Status Instruments website – 

http://www.status.co.uk 

for a wide range of temperature and process equipment 

with direct PC to instrument USB configuration, removing the need for a configuration module altogether.

AC

USB-CONFIG-MKII

Power Lead

USBTTX

-

+

TTR200X
TTC200X

CONNECTION OPTIONAL

AC

USB-CONFIG-MKII

Power Lead

USBTTX

-

+

CONNECTION OPTIONAL

SEM1801XR
SEM1802XR
SEM1801XTC
SEM1802XTC

RED WIRE

RED WIRE

BLACK WIRE

BLACK WIRE

5.3  Indoor use only.  The temperature sensor must be located in the safe area when being used with the USBTTX Config.  For use with 
TTC200X, TTR200X, SEM1801XTC – SEM1802XTC and SEM1801XR- SEM1802XR temperature sensors certified under IECEx TRC 
10.0008X & TRAC09ATEX11232X

Reviews: