background image

USER TRIM

Supply

User  trim  function  allows  manual  adjustment  of  the  analog  output,  this  is  useful  for  minor  calibration  adjustment  or 
trimming out any sensor error, ± 5 % of range adjustment is available at both offset and span.  Raise and lower buttons 
are  provided  on  the  front  panel  of  the  transmitter,  accessed  using  a  3  mm  flat  blade  screw  driver.  Insert  the  screw 
driver into the appropriate slot to operate the button. The button has a click action. 

The transmitter will automatically detect the correct trim point (offset or span) based on the output signal. Offset will be 
trimmed when the current in the offset band,  span when the current is in the span band. No trim action occurs at any 
other  current.  Note  this  function  needs  to  be  selected  by  the  software  configuration  tool  before  use.  To  lock  settings 
after  adjustment  the  operator  can  again  use  the  tool  to  turn  this  function  off,  (select  the  option  to  save  trim  when 
downloading configuration).

METHOD
1.0    Connect    transmitter  to  a  suitable  input  simulator  or  sensor. 
Connect  supply,  connecting  a  digital  meter  to  monitor  output.  
Turn supply on, set input to  offset/span   calibration point.  
IMPORTANT  -  IF  PERFORMING  TWO  POINT  CAL,  ALWAYS  CAL 
OFFSET FIRST.

2.0 Enter trim menu by pressing "raise" button for two  seconds.
When the trim menu is open the range LED will flash :-

+

-

Screw Driver

Ø 3 mm

20.000 

   

Digital mA meter

Input Simulator

 or sensor

Output 

Signal

offset

span

Range

Offset

Span

(4 to 20) mA

(3.8 to 6) mA

(18 to 22) mA

(0 to 20) mA

(0 to 2) mA

(18 to 22) mA

User mA 

User low ± 2 mA (Min 0 mA)

User High ± 2 mA (Max 24 mA)

(0 to 10) V

(0 to 1) V

(9 to 11) V

UserV 

User low ± 1 V (Min 0 V)

User High ± 1 V (Max 12 V)

Enter

Green Ok LED will indicate Trim action

 > 2 s

3.0  Trim  output  current  by 
pressing  either  the  raise  or 
lower  button,  single  click  to 
step  advance,  or  press  contin-
uously to auto advance.

4.0  Once  trim  is  complete  allow 
30  seconds  with  no  button 
press,  the  transmitter  will  time 
out 

and 

return 

to 

normal 

operation.

Raise

Lower

Escape

> 30 s

USER RANGE CONFIGURATION

This  function  allows  two  point  manual  configuration  of  the  re-transmission  current  (voltage)  at  low  and  high  range  against  a  live  input 
signal. This is useful for on-site configuration, example with a slide wire input the user manually position the slide at both low and high 
position  and  configures  the  unit  to  operate  over  this  range.  Configuration  is  achieved  using  either  the  raise  (span)  or  lower  (offset) 
buttons.
To operate this function it must first be selected using the software configuration tool. The operator may lock this function (once set) by 
turning off the function.

METHOD

1.0 Connect  transmitter to a suitable input simulator or sensor. Connect supply, turn supply on, set input to either offset or span calib-
ration point. 

2.0 To enter configuration, set input to desired high or low 
setting and wait 10 seconds. Press and hold raise(high) or 
lower(low) button on for 2 seconds to enter.

The Ok LED will then start to flash at a slow rate (low) or fast 
rate(high).

3.0 Once  the  menu  has  been  entered,  quickly  (within  1  second) 
apply a single press the the raise(high) lower(low) button to store 
setting. 
To  abort  configuration,  allow  configuration  to  time  out  by  not 
pressing buttons for 5 seconds.

Ø 3 mm

Screw Driver

Input Simulator

 or sensor

+

-

Low- slow toggle 

High fast toggle 

Input out of range

 > 2 s

Enter High scale 

config

Enter Low scale 

config

 < 1 s

Single Press

Store High scale config

Store Low scale config

Green Ok LED will indicate Trim action

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

17

18

16

TRIP 1 (A)

A

B

C

14

15

13

TRIP 2 (B)

Action

Normal 

Trip

Range  Error

Power off

Hi_ Al

Lo_Al

Hi_ Con

Lo_Con

OUTPUT DAMPING

User adjustable damping of the analog output is provided for both rising and falling signal. The adjustable range is (0 to 250) second for a ( 0 to 20) mA or 
(0 to 10) V swing. To calculate rate of change of output signal divide 20mA (10 V) by damping setting, example if damping is set to 100 seconds the mA 
output will change at a rate of (20/100) = 0.2 mA /Second.  Use USB_LINK software to configure damping setting. 

TRIP OUTPUTS

Dual trip SPDT relays are available. The contacts are rated at 240 V ac 1 A (Non inductive) 30 V DC 1 A. An external snubber network is recommended when 
switching inductive circuits. Please ensure the snubber network is rated for the application. Four actions are provided, as detailed in the diagram  below. 
The Alarm actions may also be used for inverted control applications, example the high alarm action can be used to control a cooling fan when used to 
control  the  temperature  of  a  heat  source.  Ajustable  setpoint  and  deadband  are  provided  together  with    adjustable  on  and    off  delays  for  each  trip.    The 
delay range is  ( 0 to 250 ) Seconds. 

SP

DB

Hi_Alrm 

Trip 

Led

Lo_Alrm

SP

Trip 

Led

DB

Hi_Ctrl

Trip 

Led

SP

DB

Lo_Ctrl

SP

Trip 

Led

DB

Offset slow toggle 

Span fast toggle 

Out of trim range

Input out of range

Reviews: