5 Permanent Installation
5.1 Where to Install
The Portawattz 3000 should be installed in a location that meets the
following requirements:
• Dry - Do not allow water to drip or splash on the Portawattz
3000.
•Cool - Ambient air temperature should be between 0ºC and
25ºC (32ºF and 77ºF). The cooler the better.
• Ventilated - Ensure that the unit is in a compartment that is
ventilated, and that you allow at least 1 inch
(2.5cm) of clearance around the Portawattz 3000
for air flow. Ensure that ventilation openings on
the front and rear of the unit are not obstructed.
• Safe - Do not install the Portawattz in the same compartment
as batteries or in any compartment capable of storing
flammable liquids such as gasoline (see warning
below).
• Close to Battery - Install as close to the battery as possible in
order to minimize the length of cable
required to connect the inverter to the
battery, but not in the same compartment.
It is better and cheaper to run longer AC
wires than longer DC cables, because of
the much lower currents in the AC wires.
Mount the Portawattz on a flat surface using the mounting flanges on
the front and rear panels. Mounting hardware should be corrosion
resistant and #10 or larger. The Portawattz may be mounted
horizontally or vertically.
CAUTION!
To reduce fire hazard, do not cover or obstruct ventilation openings. Do not
install the Portawattz 3000 in a zero-clearance compartment. Overheating
may result.
WARNING!
This equipment contains components which tend to produce arcs or sparks.
To reduce risk of fire or explosion do not install in compartments containing
batteries or flammable materials or in locations which require ignition protected
equipment.