background image

31

four concentric terminations

Four concentric terminations may be installed in close proximity 

as shown in Figure 38. See Figure 34 and Figure 35 on page 31 

for detailed information on clearances and additional arrangement 

options.

SIDEWALL

ROOF

figure 38

eight concentric terminations

Eight  concentric  terminations  may  be  installed  in  two  stacked 

groups of four, in close proximity, as shown in Figure 39. See 

Figure 36 on page 31 for detailed information on clearances. 
Lateral groups of four as shown in Figure 35 on page 31 may be 

a more convenient installation arrangement for multiple groups 

depending on available space.

SIDEWALL

ROOF

figure 39

multiple concentric termination arrangements

The  illustrations  on  this  page  show  some  of  the  installation 

arrangements  for  multiple  concentric  terminations  that  are 

allowed.
See multiple Concentric Termination Clearances on page 31 for 

detailed information on clearances and additional arrangement 

options.

note:

  When  multiple  concentric  terminations  are  installed 

through a roof in the same location all termination caps must be 

at the same height measured from the ground. 

two concentric terminations

Two concentric terminations may be installed in close proximity 

as  shown  in  Figure  37  or  with  standard  clearances  when  this 

arrangement  is  not  possible.  See  Figure  32  on  page  31  for 

detailed information on clearances. See Figure 33 on page 31 

when installing three concentric terminations.

SIDEWALL

ROOF

figure 37

Summary of Contents for SUF-130- 300/400/500

Page 1: ...RATION SERVICE MAINTENANCE LIMITED WARRANTY 500 Tennessee Waltz Parkway Ashland City TN 37015 WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try ...

Page 2: ... Wiring Diagrams 66 Water Piping Diagrams 67 Limited Warranty 74 Table Of Contents Safe Installation Use and Service 3 General Safety Information 4 Precautions 4 Introduction 6 Qualifications 6 iCOMM BACnet Compatible 6 Preparing For The Installation 6 Features And Components 7 Basic Operation 7 Top View 8 Side Views 9 Installation Considerations 10 Rough In Dimensions 10 Recovery Capacities 10 Lo...

Page 3: ...ause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical known to the State of California to cause cancer birth defects or other reproductive harm This appliance can cause low level exposure to some of the substances listed in the Act DANGER WARNING CAUTION CAUTION DANGER indicates an imminently h...

Page 4: ...h as air escaping through the pipe as the water begins to flow There should be no smoking or open flame near the faucet at the time it is open General Safety Information Read and understand this instruction manual and the safety messages herein before installing operating or servicing this water heater Failure to follow these instructions and safety messages could result in death or serious injury...

Page 5: ...iment trap in accordance with NFPA 54 Use joint compound or Teflon tape compatible with propane gas Fire and Explosion Hazard Turn off gas lines during installation Contact a qualified installer or service agency for installation and service Excessive gas pressure to gas valve can cause serious injury or death Do not use water heater with any gas other than the gas shown on the rating label Turn o...

Page 6: ...on Detailed installation diagrams are also found in this manual These diagrams will serve to provide the installer with a reference It is essential that all venting water piping gas piping and wiring be installed as shown Particular attention should be given to the installation of thermometers at the locations indicated in the piping diagrams as these are necessary for checking the operation of th...

Page 7: ...SOR MAIN BURNER radial design BLOWER FLANGE INTAKE AIR combustion air CONNECTION 4 INCH PVC Figure 2 Hot Surface Igniter The control system energizes the Hot Surface Igniter with 120 VAC during the igniter warm up period When the igniter is energized it produces sufficient heat 1800 F 982 C to ignite the Main Burner Note Care must be taken when handling the igniter to prevent breakage During the i...

Page 8: ... Control System Operation on page 8 Top View 3 2 4 5 6 7 9 11 13 12 2 14 15 17 1 18 16 10 8 FRONT Top View Components 1 Water Heater s 120 VAC on off switch 2 Powered anode rods The water heater s covered in this manual are equipped with two powered non sacrificial anode rods Protective current is fed by the control system to the titanium electrodes at the end of each anode rod This current flows ...

Page 9: ...age 9 and Condensate Drain Installation on page 9 Side Views 1 Cleanout access panel covers water heater cleanout opening 2 CCB enclosure see Figure 3 on page 9 for description 3 120 VAC junction box Incoming power supply and ground connections are made here see requirements for Power Supply on page 9 4 Intake air connection 4 inch PVC 5 Supply gas line connection See Supply Gas Line on page 9 6 L...

Page 10: ... 72 C 78 C SUF 130 300 Natural 300 000 88 GPH 1746 1164 873 699 582 499 436 388 349 318 291 269 250 Propane LPH 6610 4406 3304 2644 2203 1888 1652 1469 1322 1201 1102 1017 945 SUF 130 400 Natural 399 900 117 GPH 2328 1552 1164 931 776 665 582 517 466 423 388 359 332 Propane LPH 8813 5875 4406 3525 2938 2518 2203 1958 1763 1602 1469 1356 1259 SUF 130 500 Natural 499 900 146 GPH 2878 1919 1439 1151 ...

Page 11: ... page 11 Fire or Explosion Hazard Read instruction manual before installing using or servicing water heater Avoid all ignition sources if you smell gas Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Use only the gas shown on the water heater rating label Keep ignition sources away from faucets after extended periods of non use Main...

Page 12: ...ee Circulation Pump Wiring Diagrams on page 12 for electrical hookup information Install in accordance with the current edition of the National Electrical Code NFPA 70 or the Canadian Electrical Code CSA C22 1 All bronze circulators are recommended for used with commercial water heaters Some circulating pumps are manufactured with sealed bearings and do not require further lubrication Some circula...

Page 13: ...tified for use without modification for altitudes up to 10 000 feet For elevations above 10 000 feet 3 048 meters see High Altitude Installations on page 13 Minimum supply gas pressure readings are taken while gas is not flowing static pressure AND while gas is flowing dynamic pressure Supply pressure must never fall below the minimum values Supply gas pressures should be measured with all gas fir...

Page 14: ...urns instantly resulting in severe injury or death Children the elderly and the physically or mentally disabled are at highest risk for scald injury Feel water before bathing or showering Temperature limiting devices such as mixing valves must be installed when required by codes and to ensure safe temperatures at fixtures Water heated to a temperature which will satisfy clothes washing dish washin...

Page 15: ...ter heater is provided with a properly rated sized and certified combination Temperature Pressure Relief Valve T P valve by the manufacturer The valve is certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief Valves for Hot Water Supply Systems ANSI Z21 22 CSA 4 4 and the code ...

Page 16: ...son See Condensate Drain Installation on page 16 Combustible Material Storage Fire or Explosion Hazard Read instruction manual before installing using or servicing water heater Avoid all ignition sources if you smell gas Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Use only the gas shown on the water heater rating label Keep igni...

Page 17: ... the size of opening required to provide the free area specified Where the louver and grille design and free area are not known it shall be assumed that wood louvers will have 25 free area and metal louvers and grilles will have 75 free area Non motorized louvers and grilles shall be fixed in the open position Air Requirements Breathing Hazard Carbon Monoxide Gas Install water heater in accordance...

Page 18: ...regate input rating of all appliances installed in the enclosure When ducts are used they shall be of the same cross sectional area as the free area of the openings to which they connect The minimum dimension of rectangular air ducts shall be not less than 3 inches Fresh Air Openings For Confined Spaces The following instructions shall be used to calculate the size number and placement of openings...

Page 19: ...s section of the manual are a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Venting Installation on page 19 for complete venting installation instructions Figure 13 The confined space shall be provided with two permanent vertical ducts one commencing within 12 inches 300 mm of the top and one...

Page 20: ...minal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size gas vent directly below Keep clear of all obstructions Installation Requirements Commonwealth of Massachusetts Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unl...

Page 21: ...ace or if the pipe cannot move freely through a wall penetration the pipe may be stressed or high thermal stresses may be formed when the pipe heats up and expands Install accordingly to minimize such stresses 19 Carefully read the Venting Requirements on page 21 and then proceed to the Venting Installation Sequence on page 21 Venting Installation Breathing carbon monoxide can cause brain damage o...

Page 22: ...hone number listed on the back cover of this manual to order 4 Concentric Termination Part 9006328005 6 Concentric Termination Part 9006144005 Venting Requirements Approved Materials Approved vent and intake air pipe materials that may be used in the United States PVC Schedule 40 ASTM D 2241 CSA B181 2 ASTM D 1785 CSA B137 3 CPVC Schedule 40 ASTM F 411 CSA B137 6 ABS ASTM D 2661 Approved vent and ...

Page 23: ...t pipes must be pitched a minimum of a 1 4 inch per foot back to the water heater to allow drainage of condensate 11 If installing 4 inch vent pipe connect the vent pipe to the exhaust elbow on the water heater 12 If installing 6 inch vent pipe transition to 4 inch pipe at the exhaust elbow on the water heater as shown in Figure 15 The field installed 4 pipe between the exhaust elbow and the 6 x 4...

Page 24: ...orizontally See Figure 20 on page 24 4 If installing only vent piping in a Power Vent configuration vertically through the roof the following instructions must be followed The vent termination must be oriented facing downward as shown in Figure 19 and Figure 20 on page 24 The bottom edge of the vent termination must be a minimum of 12 inches 30 cm 18 inches 45 cm in Canada above the average or exp...

Page 25: ...ions must have a minimum separation of 24 61 cm measured on center line as shown in Figure 21 on page 25 In colder climates this separation should be increased to at least 48 inches 122 cm The bottom edge of the intake air and vent terminations must be a minimum of 12 inches 30 cm 18 inches 45 cm in Canada above the average or expected snow level as shown in Figure 19 and Figure 21 on page 25 6 Wh...

Page 26: ...r hole for 6 inch pipe where the pipe s will pass through the wall Note Beware of concealed wiring and piping when cutting through the wall 8 Cut a length s of pipe being installed 3 5 inches 8 9 cm to 9 5 inches 24 1 cm longer than the wall thickness at the opening See Figure 23 Note Vent Termination exhaust gases of this water heater are less than 140 F In cold climates water vapor in the exhaus...

Page 27: ...all or structure as shown in Figure 24 and Figure 25 Note If this required distance to a parapet vertical wall or structure cannot be maintained standard terminations must be used See Vertical Termination Installation on page 27 5 When installing a concentric termination through a sidewall ensure that all exterior sidewall clearance requirements for the termination shown in Figure 49 on page 27 ar...

Page 28: ... assembly and secure it to the roof 5 Seal around the plumbing boot or roof flashing 6 Cement the vent cap onto the vent pipe Alternately a field supplied stainless steel screw may be used to secure the 2 components together when field disassembly is desired for cleaning A pilot hole must be drilled for the screw to prevent damage cracking of the vent cap and or vent pipe 7 Install the vent cap ve...

Page 29: ...LIED LENGTH 25 3 8 INCHES 64 cm MAXIMUM ALLOWABLE LENGTH 45 3 8 INCHES 115 cm MINIMUM ALLOWABLE LENGTH 12 INCHES 30 cm VENT CAP STAINLESS STEEL VENT TERMINAL WITH SCREEN INTAKE AIR PIPE INTAKE AIR CONNECTION 6 or 4 PVC VENT CONNECTION 4 PVC 6 x 4 STANDARD REDUCER BUSHING 6 x 6 x 6 Y FITTING 6 x 4 NO STOP LIP REDUCER BUSHING INTAKE AIR PIPE Y FITTING ASSEMBLY VENT CAP VENT PIPE ASSEMBLY Figure 29 A...

Page 30: ...ations are maintained Ensure multiple terminations are arranged or grouped as required Note These clearances must be maintained to prevent the recirculation of vent exhaust gases to the intake air Clearances are measured between the edges of the concentric termination caps When installing multiple concentric terminations through a roof or through a sidewall the clearances shown in Figure 32 must b...

Page 31: ...WALL ROOF Figure 39 Multiple Concentric Termination Arrangements The illustrations on this page show some of the installation arrangements for multiple concentric terminations that are allowed See Multiple Concentric Termination Clearances on page 31 for detailed information on clearances and additional arrangement options Note When multiple concentric terminations are installed through a roof in ...

Page 32: ...32 Venting Arrangements Power Vent Vertical Figure 40 Direct Vent Vertical Figure 42 Power Vent Horizontal Figure 41 Direct Vent Horizontal Figure 43 ...

Page 33: ...ng Arrangements Direct Vent Vertical Vent Horizontal Intake Figure 44 Direct Vent Vertical Concentric Figure 46 Direct Vent Horizontal Vent Vertical Intake Figure 45 Direct Vent Horizontal Concentric Figure 47 ...

Page 34: ...nto building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30kW 36 inches 91cm for appliances above 100 000 Btu hr 30 kW 4 feet 1 2 m below or to side of opening 1 foot 30 cm above opening D Vertical clearance to ventilated soffit located above the terminal within a ...

Page 35: ...t into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30 kW 36 inches 91 cm for appliances above 100 000 Btu hr 30 kW 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 9 inches 23 cm for appliances between 10 000 Btu hr 3 kW and 50 000 Btu hr 15 kW 12 in...

Page 36: ...required for installation include Approved PVC cement and PVC primer 1 2 inch PVC pipe minimum length to equal the distance between the water heater and a suitable building drain 1 2 inch PVC fittings elbows and couplings necessary to install a condensate drain line between the Condensate Drain Trap Assembly and a suitable building drain Floor mounted standoffs to brace the drain line Installation...

Page 37: ... VALVE TEE FITTING PIPE CAP SEDIMENT TRAP DIRT LEG Figure 52 Ensure all gas pipe is clean on the inside before installation To trap any dirt or foreign material in the gas supply line a sediment trap dirt leg must be installed as shown in Figure 52 The sediment trap must be readily accessible and not subject to freezing conditions Install in accordance with the recommendations of the local gas uti...

Page 38: ...ut off turn off the Main Gas Shutoff valve to the water heater Gas Line Leak Testing Fire and Explosion Hazard Leak test before placing the water heater in operation Disconnect gas piping and main gas shutoff valve before leak testing Install sediment trap in accordance with NFPA 54 Use joint compound or Teflon tape compatible with propane gas Any time work is done on the gas supply system perform...

Page 39: ... water heater caused by freezing temperatures is not covered under the limited warranty Electrical Wiring AllelectricalworkmustbeinstalledinaccordancewiththeNational Electrical Code ANSI NFPA 70 or the Canadian Electrical Code CSA C22 1 and local requirements When installed the water heater must be electrically grounded in accordance with local codes or in the absence of local codes with the Natio...

Page 40: ...Mixing Valves on page 40 2 Dishwashing Machines on page 40 3 Temperature Pressure Relief Valve on page 40 4 Closed Systems and Thermal Expansion on page 40 5 For multiple water heater installations see Water Piping Diagrams beginning on page 40 Water Piping Diagrams This manual provides detailed water piping diagrams for typical methods of application for the water heaters see Water Piping Diagram...

Page 41: ...mperature Probe two red wires see Figure 3 on page 41 for location The ECO switch contacts will open when the water temperature reaches approximately 202 F 94 C and close at approximately 140 F 49 C If the ECO activates contacts open due to abnormally high water temperatures in the storage tank the control system will immediately de energize the 24 VAC Gas Valve and end the current heating cycle T...

Page 42: ...e storage tank Heating cycles and ignition are managed by the control system The ECO energy cut out flame sensor pressure switches and temperature probes are monitored by the control system The Combustion Blower igniter 24 VAC Gas Valve and anode rods are all powered by the control system The main components of the control system are a UIM user interface module and a CCB central control board The ...

Page 43: ...e See Figure 3 on page 43 for Blower Prover Switch location The Hot Surface Igniter is being energized See Figure 2 on page 43 for Hot Surface Igniter location The igniter has been energized and the control system has sensed the required minimum igniter current The check mark icon is visual confirmation of minimum igniter current See the Sequence Of Operation on page 43 for minimum current AC amps...

Page 44: ...s from the combustion chamber at the end of a heating cycle Fault The control system has detected a Fault condition Heating operation is disabled until the Fault condition is corrected Power to the water heater must be cycled off and on to reset the control system Note Cycling power will not reset the control system if the condition that caused the Fault has not been corrected Control System Menus...

Page 45: ...all control system menus from the Main Menu With Temperatures menu selected highlighted in black in the Main Menu screen press the Operational Button under SELECT to enter the Temperatures menu If the Temperatures menu is not selected use the Up and Down Buttons to select this menu item Temperatures Heater Status Display Settings Heater Information Current Fault SELECT BACK HELP Main Menu With the...

Page 46: ...robe Offset 0 F CHANGE BACK HELP Temperatures Bottom of Menu Differential 8 F Tank Temperature 120 F Upper Temperature 122 F Lower Temperature 118 F Heater Regulated to Tank Upper Probe Offset 0 F Lower Probe Offset 0 F CHANGE BACK HELP Temperatures Heater Status Menu Description Action Display Select Heater Status from the Main Menu and press the Operational Button under SELECT to enter this menu...

Page 47: ...ted time the control system water heater has been energized Burner On Time Total accumulated time the control system has been in the heating operating state burner run time Cycle Count Total accumulated count of heating cycles CCB Version Software version for central control board UIM Version Software version for user interface module Note Historical data is stored in the CCB s memory If this CCB ...

Page 48: ... event will replace the oldest Press the Operational Button under VIEW to view details for each Fault or Alert message stored 1 Blocked Air Intake A7 51 mins ago 2 Blocked Exhaust A8 54 mins ago 3 Low Gas Pressure A6 57 mins ago 4 Blower Prover Failure AC VIEW BACK HELP Fault History Fault Occurrence Description Action Display Select Fault Occurrence from the Main Menu and press the Operational Bu...

Page 49: ...his menu item Show Contact Information Yes Change Contact Name Change Contact Phone Current Contact Info 000 000 0000 Access Code UPDATE CANCEL Service Contact Information Using the UP and DOWN buttons select highlighted in black the Change Contact Name menu item Press the Operational Button under SELECT to open the Change Contact Name menu Show Contact Information Yes Change Contact Name Change C...

Page 50: ... found Initial Start Up Required Test Equipment Two U tube manometers recommended ranges 0 14 W C 0 3 5 kPa and 0 35 W C 0 8 7 kPa or pressure gauges Two digital manometers can be used in place of U tube manometers or pressure gauges Recommended ranges 14 00 to 14 00 W C 0 3 5 kPa resolution 0 01 W C and 0 35 W C 0 8 7 kPa resolution 0 10 W C Note All test equipment must be acclimated to ambient t...

Page 51: ...re than 1 4 turn and allow the manifold gas pressure to stabilize for several minutes before making further adjustments 4 Replace the gas pressure regulator cover screw 5 Cycle the burner on and off several times to check operation 6 Compare the actual manifold gas pressure reading recorded above to the required minimum maximum values given in Table 4 on page 51 Adjust manifold gas pressure as nec...

Page 52: ...tment on page 52 2 When the water heater has completed its shut down sequence and enters the standby mode turn the water heater s on off switch to the off position 3 Push in the gas control knob slightly and turn to the off position see Figure 56 on page 52 and Figure 57 on this page 4 Close the Main Gas Shutoff Valve see Figure 52 on page 52 High Altitude Installations Fire and Explosion Hazard G...

Page 53: ...ult in fire or explosion Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle o...

Page 54: ...d the state of other system devices If the tank temperature drops below the Operating Set Point minus the Differential setting the control will automatically return to Step 2 and repeat the operating cycle Troubleshooting Installation Checklist The list below represents some of the most critical installation requirements that when overlooked often result in operational problems down time and needl...

Page 55: ...for warm up period 24 VAC Gas Valve is energized gas flows to Main Burner Is flame sensed at the Main Burner control system monitors the flame sensor Control System Locks Out Displays Fault Msg NO Control System Locks Out Blower Prover Open Fault Msg is displayed NO Control System Locks Out Low Igniter Current Fault Msg is displayed NO Combustion Blower is energized Pre Purge cycle Does Control Sy...

Page 56: ...e disable circuit disabling heating operation See Enable Disable Circuit on page 56 The heating capacity of the water heater has been exceeded the water heater is unable to meet demand Operational Problems Read and understand this instruction manual and the safety messages herein before installing operating or servicing this water heater Failure to follow these instructions and safety messages cou...

Page 57: ...n which can cause a fire or explosion Colder incoming water temperature lengthening the time required to heat water to desired temperature Hot water piping leaks open faucets water heater drain valve leaking or open Sediment or lime scale accumulation may be affecting water heater operation See Maintenance on page 57 for sediment and lime scale removal procedures Water heater not firing at full in...

Page 58: ...essure is below the required minimum pressure see Table 4 on page 58 Supply gas is turned off at the Main Shutoff Valve Supply gas pressure is dropping when other gas fired appliances on a common supply gas line are operating Low volume of supply gas see Supply Gas Line Installation on page 58 and the requirements for the Supply Gas Line on page 58 and Supply Gas Regulator on page 58 CHANGE BACK A...

Page 59: ... page 59 for switch location Excessive equivalent pipe length exceeded the maximum number of 90 elbows or wrong pipe size used in the intake air piping system see Venting Requirements on page 59 Balance plate and or intake air screen was not removed prior to connecting the intake air piping to the water heater and is clogged blocked with debris see Figure 17 on page 59 Excessive negative air press...

Page 60: ...e General Keep appliance area clear and free from combustible materials gasoline and other flammable vapors and liquids See Locating The Water Heater on page 60 Water heater maintenance includes periodic tank flushing and cleaning and removal of lime scale The water heater should be inspected and adjusted to maintain proper combustion See Initial Start Up on page 60 A periodic inspection of the ve...

Page 61: ...r hot Then close the hot water faucet 4 Connect a hose to the drain valve and terminate it to an adequate drain 5 Ensure the drain hose is secured before and during the entire flushing procedure Flushing is performed with system water pressure applied to the water heater 6 Open the water heater drain valve to flush the storage tank 7 Flush the water heater storage tank to remove sediment and allow...

Page 62: ...re factory equipped with a powered anode system The anode rods 2 are of a permanent design and do not need replacing unless damaged Inspection and cleaning should be performed once a year Note Follow the instructions to drain the water heater storage tank on page 62 first Remove the powered anodes from the water heater by loosening the 3 4 NPT bushing that forms the top of the anodes Do not disass...

Page 63: ... numbers 1 4 On the other side of the dipswitch is the word OPEN The dipswitches are rocker type switches if one side of the rocker is down the other side will be up Pressing a rocker down on the side of the array labeled OPEN opens the switch Pressing a rocker down on the side of the array labeled with the numbers 1 4 closes the dipswitch CHANGING NUMBER OF IGNITION TRIALS BEFORE LOCK OUT NOTE Al...

Page 64: ...ALVE B CENTRAL CONTROL BOARD C C 6 J 5 J 4 J 7 J 5 1 J 6 1 J 0 1 J 3 1 J 2 J 3 J 1 J TRANSFORMER INSIDE CCB ENCLOSURE 50VA GROUND STRIP BURNER GROUND BURNER BOLT ON OFF SWITCH GROUND 120 VAC NEUTRAL 120 VAC HOT LOW GAS PRESSURE SWITCH 1 BLACK 2 WHITE RED 1 BLACK 2 BLACK 1 BLACK 2 WHITE M USER INTERFACE MODULE I U 1 2 15 4 14 5 10 6 7 8 13 11 L N ANODE 1 ANODE 2 1 GREEN 2 BLUE 2 RED GREEN WHITE N O...

Page 65: ...BLOWER PROVER 24 VAC GAS VALVE B C C 6 J 5 J 4 J 7 J 5 1 J 6 1 J 0 1 J 3 1 J 2 J 3 J 1 J TRANSFORMER 50VA GROUND STRIP BURNER GROUND BURNER BOLT LOW GAS PRESSURE SWITCH 1 BLACK RED 2 WHITE 1 BLACK 2 BLACK M I U 1 2 15 4 14 5 10 6 7 8 13 11 L N ANODE 1 ANODE 2 1 GREEN 2 BLUE N O I T C N U J X O B RED GREEN GREEN WHITE N E E R G N E E R G N E E R G GREEN UPPER TEMPERATURE PROBE 1 BLACK120 VAC HOT 3 ...

Page 66: ...CIRCUIT DO NOT SHARE POWER WITH APPLIANCE AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION CIRCULATING PUMP WIRING DIAGRAM DISHWASHER LOOP WITH TOGGLE SWITCH FIELD SUPPLIED TEMPERATURE CONTROL INSTALLED IN THE CIRCULATING LOOP RETURN LINE DISHWASHER TOGGLE SWITCH CIRC PUMP MOTOR L1 HOT L2 NEUTRAL 120 VAC POWER NOTE USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRC...

Page 67: ...review the following 1 See Mixing Valves on page 67 2 See Dishwashing Machines on page 67 3 See Temperature Pressure Relief Valve on page 67 ONE WATER HEATER SINGLE TEMPERATURE WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK OR LINE TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING ...

Page 68: ...nes on page 68 3 See Temperature Pressure Relief Valve on page 68 ONE WATER HEATER TWO TEMPERATURE WITH HIGH TEMPERAURE LOOP RECIRCULATION WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE MIXING VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHE...

Page 69: ...alve on page 69 ONE WATER HEATER SINGLE TEMPERATURE WITH VERTICAL STORAGE TANK FORCED RECIRCULATION WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ...

Page 70: ...ONE WATER HEATER SINGLE TEMPERATURE WITH HORIZONTAL STORAGE TANK FORCED RECIRCULATION WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE MIXING VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR A...

Page 71: ...ollowing 1 See Mixing Valves on page 71 2 See Dishwashing Machines on page 71 3 See Temperature Pressure Relief Valve on page 71 TWO WATER HEATERS SINGLE TEMPERATURE WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGUR...

Page 72: ...e Mixing Valves on page 72 2 See Dishwashing Machines on page 72 3 See Temperature Pressure Relief Valve on page 72 THREE WATER HEATERS SINGLE TEMPERATURE WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND O...

Page 73: ...lves on page 73 2 See Dishwashing Machines on page 73 3 See Temperature Pressure Relief Valve on page 73 FOUR WATER HEATERS SINGLE TEMPERATURE WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES...

Page 74: ...he heater s and operational at all times The temperature and pressure relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will provide only a replacement water heater or part thereof The owner is responsible for all other costs Such costs may include but are not limited to a Labor charges for service removal repair...

Page 75: ...75 ...

Page 76: ...500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 365 0024 Fax 800 644 9306 www statewaterheaters com ...

Reviews: