Servicing should only be performed by a Qualified Service Technician
STEP 2: TEST FOR 24VAC BETWEEN BLACK AND ORANGE ON DAMPER PC
BOARD
IF
THEN
24VAC is present - damper NOT opening
•
Check Service Switch Position. Replace Damper
Assembly.
24VAC is not present.
•
Check Wiring Harness to Thermostat.
24VAC present - Damper Opens
•
Continue to Step 3.
CONDITION:
•
Damper rotates continuously.
STEP 3: TEST THE THREE AMP FUSE
CONDITION:
•
Test via the terminals on the head of the fuse or by removing the fuse and testing across the blades.
•
Verify that there is 120 VAC to the thermostat. Once verified set the meter to check for continuity and
perform the checks shown in figure below and on next page.