background image

1

Instruction Manual

PRINTED 0912 

195202-004

place these InstructIons adjacent to heater and notIfy owner to keep for future reference.

coMMercIal electrIc water heaters 

Thank you for buying this energy efficient water heater. 
We appreciate your confidence in our products.

Models

pce-6/10/17/20 10Msa series 102

pce-30/40/50 2olsa series 110

& pce-30/40/52/66/82/120 2orta series 110

InstallatIon - operatIon - serVIce  

- MaIntenance - lIMIted warranty

500 Tennessee Waltz Parkway

Ashland City, TN 37015

Summary of Contents for PCE-10 10MSA

Page 1: ...L ELECTRIC WATER HEATERS Thank you for buying this energy efficient water heater We appreciate your confidence in our products MODELS PCE 6 10 17 20 10MSA Series 102 PCE 30 40 50 2OLSA Series 110 PCE 30 40 52 66 82 120 2ORTA Series 110 INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY 500 Tennessee Waltz Parkway Ashland City TN 37015 ...

Page 2: ... testing or replacement of gas piping or b the connection installation testing repair or servicing of appliances and equipment that is experienced in such work that is familiar with all precautions required and that has complied with all the requirements of the authority having jurisdiction DANGER WARNING CAUTION DANGERindicatesanimminentlyhazardous situation which if not avoided will result in de...

Page 3: ...lowed in all cases This water heater must be connected to a grounded metal permanent wiring system or an equipment grounding conductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the water heater Hydrogen Gas Flammable Hydrogen gas can be produced in a hot water system served by this heater that has not been used for a long period of time ge...

Page 4: ...al Code CSA C22 1 The National Electrical Code may be ordered from National Fire Protection Association 1 Batterymarch Park Quincy MA 02269 The Canadian Electrical Code is available from the Canadian StandardsAssociation 8501 East Pleasant Valley Road Cleveland OH 44131 3 If after reading this manual you have any questions or do not understand any portion of the instructions call the toll free num...

Page 5: ...000 GPH 113 101 75 68 56 51 45 41 38 34 32 10 LPH 426 384 284 256 213 192 170 153 142 128 122 6000 6000 GPH 135 122 90 81 68 61 54 49 45 41 39 12 LPH 511 460 341 307 256 230 205 184 170 153 146 Recovery capacities at 100 F rise equal for non simultaneous element operation 4 1 gal x KW of one element for simultaneous element operation 4 1 gal x 2 3 KW of both elements For other rises multiply eleme...

Page 6: ...6 APPROVALS model and rating PCE 30 40 50 2OLSA PCE 30 40 52 66 80 120 2ORTA PCE 6 10 17 20 1OMSA All models are listed by Underwriters Laboratories Inc ...

Page 7: ...OPER INSTALLATION INSTALL IN ACCORDANCE WITH ALL LOCAL CODES INSTALL VACUUM RELIEF IN COLD WATER INLET LINE AS REQUIRED BY LOCAL CODES INSTALL SUITABLE DRAIN PANS UNDER WATER HEATERS TO PREVENT DAMAGE DUE TO LEAKAGE REFER TO WATER HEATER LOCATION ON page 8 INSTALL THERMAL E X PANS I ON TANK IF CHECK VALVE OR PRESSURE REDUCING VALVE IS USED IN SUPPLY LINE PCE DUAL ELEMENT HEATER PCE SINGLE ELEMENT ...

Page 8: ...NG THE NEW WATER HEATER to a drain However unanticipated damage can be reduced or prevented by a leak detector or water shut off device used in conjunction with a piped drain pan These devices are available from some plumbing supply wholesalers and retailers and detect and react to leakage in various ways Sensors mounted in the drain pan that trigger an alarm or turn off the incoming water to the ...

Page 9: ...ximum of 125 degree F Consult a qualified installer or service agency Follow all manufacturer s Instructions for installation of these valves Before changing the factory setting on the thermostat read the Temperature Regulation section in this manual Contaminated Water This water heater shall not be connected to any heating system s or component s used with a non potable water heating appliance To...

Page 10: ...d at an adequate drain inside the building Shall not have any valve or other obstruction between the relief valve and the drain The temperature pressure relief valve must be manually operated at least once a year Caution should be taken to ensure that 1 no one is in front of or around the outlet of the temperature pressure relief valve discharge line and 2 the water manually discharged can cause b...

Page 11: ...e on J terminal to L1 It is then possible for both elements to operate at once as determined by the thermostats Regardless of element connection the heater operates in an unbalanced fashion The heater may be field converted to single phase operation by moving the wire on L3 of the terminal block to L2 L3 is not used see page 12 The heater now in single phase non simultaneous operation may be field...

Page 12: ...12 Figure 3 WIRING DIAGRAMS C 2 CIRCUIT FOR SINGLE ELEMENT HEATERS EQUIPPED WITH HIGH LIMIT CONTROL A 8 CIRCUIT FOR DUAL ELEMENT HEATER FACTORY WIRED FIELD WIRING WHITE FOR 120V 277V ...

Page 13: ... for tightness Also check connections on top and or sides of heater Repair water leaks and tighten electrical connections as necessary 3 Depress the red manual reset button on each Thermostat ECO combination control See Figure 5 4 Turn on the electrical disconnect switch 5 Observe the operation of the electrical components during the first heating cycle Use care as the electrical circuits are ener...

Page 14: ...110 43 normal shower temp 116 47 pain threshold 116 47 35 minutes 45 minutes 122 50 1 minute 5 minutes 131 55 5 seconds 25 seconds 140 60 2 seconds 5 seconds 149 65 1 second 2 seconds 154 68 instantaneous 1 second U S Government Memorandum C P S C Peter L Armstrong Sept 15 1978 Figure 4 Temperature Adjustment The water temperature is controlled by surface mounted thermostats with ECO high limit Th...

Page 15: ... not affect water s taste or color The rod must be maintained to keep tank in operating condition Anode deterioration depends on water conductivity not necessarily water condition A corroded or pitted anode rod indicates high water conductivity and should be checked and or replaced more often than an anode rod that appears to be intact Replacement of a depleted anode rod can extend the life of you...

Page 16: ...ses when the heater is operating The sounds are normal however the tank bottom and elements should be cleaned See the Maintenance section of this manual Water leakage is suspected Refer to Leakage Checkpoint on the following page 17 1 Check to see if the heater drain valve is tightly closed 2 If the outlet of the relief valve is leaking it may represent Excessive water temperature Faulty relief va...

Page 17: ...sary to shut off electricity and drain tank to perform procedure Water leaks at the elements may be due to 1 Defective element which leaks at terminals or thru flange Replace element 2 Loose element gasket leak a Screw in type tighten with 1 1 2 socket wrench If leak continues remove element discard gasket and clean thread areas Apply nonhardening Permatex Number 2 to thread areas install new gask...

Page 18: ...18 nOTES ...

Page 19: ...19 nOTES ...

Page 20: ...or parts will be shipped at prevailing prices and you will be billed accordingly The model number of your Water Heater will be found on the rating plated located above the lower access panel Be sure to provide all pertinent facts when you call or visit WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING INFORMATION MODEL NUMBER VOLTAGE AND ELEMENT WATTAGE SERIAL NUMBER PART DESCRIPTION PCE 6 10 1...

Page 21: ...0 7 Instruction Manual 195202 004 195202 004 195202 004 195202 004 10 Personnel Protector 9003899015 9003899015 9003899015 9003899015 11 Pipe Nipple 194130 194130 3 194130 3 194130 3 12 Plate Knockout 43293 1 43293 1 43293 1 43293 1 PLUG 15 16 Thermostat with High Limit Switch 9003945005 9003945005 9003945005 9003945005 17 Bracket Thermostat 9003898015 9003898015 9003898015 9003898015 18 Valve Rel...

Page 22: ...896215 9003896215 6 Lower Thermostat w Hi Limit 9004533215 9004533215 9004533215 9004533215 9004533215 9004533215 9004533215 9004533215 9004533215 7 Thermostat Bracket each 9003898215 9003898215 9003898215 9003898215 9003898215 9003898215 9003898215 9003898215 9003898215 8 Personal Protector 9003899015 9003899015 9003899015 9003899015 9003899015 9003899015 9003899015 9003899015 9003899015 9 Lower ...

Page 23: ...74005 9002875005 Table 7 Incoloy Sheath Element and Wattage Chart for SMR P72 K W ELEMENT WATTAGE 120 V 208 V 240 V 277 V 480 V PART NO PART NO PART NO PART NO PART NO 1 5 1500 W 9004279005 9004283005 9004290005 9004736105 Not Available 2 0 2000 W 9004280005 9004284005 9004283005 9004290005 9004298005 2 5 2500 W 9004281005 9004285005 9004291005 9004295005 9004299005 INCOLOY ELEMENTS BELOW THIS LIN...

Page 24: ...www statewaterheaters com 500 Tennessee Waltz Parkway Ashland City TN 37015 Tech Support 800 365 0024 Parts 800 821 2017 Copyright 2012 State Water Heaters All rights reserved ...