• Provide two permanent openings to allow
circulation of combustion air.
• Make each opening 236 square inches if
they provide indoor air, and 100 square
inches for outdoor air.
• If the unit is installed in a mechanical closet,
provide a 24" clearance in front of the unit to
the door.
• If combustion air will be provided through a
duct, size the duct to provide 86 cubic feet of
fresh air per minute.
Supply combustion air to the units as per the National Fuel Gas Code, ANSI Z223.1.
Combustion Air