background image

Startco Engineering Ltd.

Page 9

SE-701 Ground-Fault Monitor

 

Rev. 0

Pub. SE-701-M, December 14, 2006.

Dimensions:

Height....................................75 mm (3.0")
Width.....................................55 mm (2.2")
Depth .....................................115 mm (4.5")

Shipping Weight...........................0.45 kg (1 lb.)

Environment:

Operating Temperature.........-40 to 60°C
Storage Temperature.............-55 to 80°C
Humidity ...............................85% Non-Condensing

Surge Withstand ...........................ANSI/IEEE 37.90.1-1989

(Oscillatory and Fast
Transient)

Certification ..................................CSA, Canada and USA

LR 53428

US

C

R

Australia

NOTES

(1)

  CSA Certification pending.

(2)

  Over operating temperature range of –40 to 60°C.

(3)

  CT accuracy not included.

(4)

  Trip time at 3 x trip-level setting.

(5)

  For maximum lead resistance of 1 

.

5.

  

O

RDERING 

I

NFORMATION

SE-701-0

1 120-Vac Supply
2 240-Vac Supply
3 24-Vac Supply
U Universal ac/dc Supply
D 9- to 36-Vdc Supply
T 30- to 70-Vdc Supply

EFCT-1............ Sensitive Earth-Fault CT,

5-A-primary rating, 82-mm (3.2") window

EFCT-1FC....... Flux Conditioner for EFCT-1,

70-mm (2.7”) window

EFCT-2............ Sensitive Earth-Fault CT, with

Flux Conditioner, 5-A-primary rating,
139-mm (5.5”) window

EFCT-26.......... Sensitive Earth-Fault CT,

5-A-primary rating,
26-mm (1”) window

PMA-55........... Panel-Mount Adapter

SE-EFVC......... Voltage Clamp

Consult factory for custom mounting adapters.

6.

  

W

ARRANTY

The SE-701 Ground-Fault Monitor is warranted to be

free from defects in material and workmanship for a
period of five years from the date of purchase.

Startco Engineering Ltd. will (at Startco’s option)

repair, replace, or refund the original purchase price of an
SE-701 that is determined by Startco to be defective if it
is returned to the Startco factory, freight prepaid, within
the warranty period.  This warranty does not apply to
repairs required as a result of misuse, negligence, an
accident, improper installation, tampering, or insufficient
care.  Startco Engineering Ltd does not warrant products
repaired or modified by non-Startco Engineering Ltd.
personnel.

Summary of Contents for SE-701

Page 1: ...SE 701 MANUAL GROUND FAULT MONITOR December 14 2006 Revision 5 Copyright 2006 by Startco Engineering Ltd All rights reserved Publication SE 701 M Document S95 C701 00000 Printed in Canada ...

Page 2: ...rip 3 2 3 3 Inhibit 3 2 4 Analog Output 3 3 Installation 3 4 Technical Specifications 8 5 Ordering Information 9 6 Warranty 9 7 Ground Fault Performance Test 10 LIST OF FIGURES PAGE 1 SE 701 Outline and Mounting Details 2 2 Typical Connection Diagram 3 3 EFCT 1 Outline and Mounting Details 4 4 EFCT 2 Outline and Mounting Details 5 5 EFCT 26 Outline and Mounting Details 6 6 PMA 55 Panel Mount Adapt...

Page 3: ...operate in applications where the ground fault current can be larger than the interrupting capacity of the device tripped by the SE 701 2 1 3 CT VERIFICATION Switch 3 is used to enable CT verification with an EFCT series CT In the CT VERIFY ON position a trip will occur if the CT is disconnected The red TRIP LED will flash to indicate a trip initiated by a CT fault Switch 3 must be in the CT VERIF...

Page 4: ...Startco Engineering Ltd Page 2 SE 701 Ground Fault Monitor Rev 4 Pub SE 701 M December 14 2006 FIGURE 1 SE 701 Outline and Mounting Details ...

Page 5: ... INHB LED s will be ON Inhibit indication is reset when the ground fault trip is reset Inhibit operation and indication will not respond if Switch 2 is in the INHIBIT OFF position 2 4 ANALOG OUTPUT The non isolated 0 to 5 V analog output indicates ground fault current sensed by the ground fault CT The output is 5 V at 100 of the CT primary rating 3 INSTALLATION An SE 701 can be surface or DIN Rail...

Page 6: ...0 121 0 80 0 30 0 20 5 30 0 138 0 MAX 126 0 56 0 46 0 4 76 0 98 4 33 0 22 0 22 0 87 3 23 2 75 2 21 4 76 3 15 1 18 0 81 1 18 5 43 4 96 2 21 1 81 M5 SCREWS TOP MOUNTING DETAIL NOTE 2 FRONT SIDE 5 0 0 20 0 FLUX CONDITIONER OPTIONAL RECESSED FOR 8 mm HEX NUT 1 0 0 04 DEEP EFCT 1 EARTH FAULT CT 600 V INSULATION CLASS STARTCO E N G I N E E R I N G L T D P P S S 2 2 1 1 FIGURE 3 EFCT 1 Outline and Mounti...

Page 7: ... 0 33 2 06 2 36 2 52 1 22 9 29 M5 SCREWS TOP MOUNTING DETAIL M4 OR 8 32 TAP SIDE FRONT E F C T 2 E A R T H F A U L T C T 6 0 0 V I N S U L A T I O N C L A S S S T A R T C O E N G I N E E R I N G L T D 5 0 0 20 DIA NOTES 1 DIMENSIONS IN MILLIMETRES INCHES MOUNTING SCREWS M4 OR 8 32 2 P P S S2 2 1 1 S P 1 1 139 7 5 50 BONDING SCREW FLUX CONDITIONER INCLUDED 26 5 1 04 FIGURE 4 EFCT 2 Outline and Moun...

Page 8: ...NTING SCREWS M4 OR 8 32 68 0 26 0 52 5 5 0 5 0 68 0 34 0 26 5 25 0 58 0 17 0 26 5 72 0 34 0 7 0 110 0 MAX 52 5 42 6 2 68 1 02 2 07 0 20 0 20 2 68 1 34 1 04 0 98 2 28 0 67 1 04 2 83 1 34 0 87 0 43 2 07 1 68 M5 SCREWS TOP MOUNTING DETAIL M4 OR 8 32 TAP FRONT SIDE 4 0 0 16 0 RECESSED FOR 7 mm HEX NUT 3 0 0 12 DEEP P P S S 2 2 1 1 EFCT 26 EARTH FAULT CT 600 V INSULATION CLASS STARTCO E N G I N E E R I...

Page 9: ...Startco Engineering Ltd Page 7 SE 701 Ground Fault Monitor Rev 5 Pub SE 701 M December 14 2006 FIGURE 6 PMA 55 Panel Mount Adapter ...

Page 10: ... On Class II Level 11 x CT Primary Rating Input Algorithms DFT Digital or Peak Digital Filter 50 to 60 Hz Bandpass CT 1 or 5 A Secondary Rating or EFCT x CT Detection Open Circuit Detection with EFCT x Thermal Withstand Continuous 5 x CT Secondary Rating 1 Second 80 x CT Secondary Rating Burden 5 A input 0 01 Ω 1 A input 0 05 Ω EFCT input 2 Ω Analog Output Range 0 to 5 Vdc 5 V 100 CT Rating Output...

Page 11: ...y rating 82 mm 3 2 window EFCT 1FC Flux Conditioner for EFCT 1 70 mm 2 7 window EFCT 2 Sensitive Earth Fault CT with Flux Conditioner 5 A primary rating 139 mm 5 5 window EFCT 26 Sensitive Earth Fault CT 5 A primary rating 26 mm 1 window PMA 55 Panel Mount Adapter SE EFVC Voltage Clamp Consult factory for custom mounting adapters 6 WARRANTY The SE 701 Ground Fault Monitor is warranted to be free f...

Page 12: ...determine the existence of alternate ground paths d Verify proper reaction of the circuit interrupting device in response to a simulated or controlled ground fault current To simulate ground fault current use CT primary current injection Fig 7 a shows a test circuit using a Startco SE 400 Ground Fault Relay Test Unit The SE 400 has a programmable output of 0 5 to 9 9 A for a duration of 0 1 to 9 9...

Reviews: