Model SCSS-700 Installation Manual
7-6
53722
7.5
Addressing SLC Devices
All SLC devices are addressed using the two rotary dials that appear on the device board. Use
the
ONES
rotary dial to set the ones place in a one or two digit number, and use the
TENS
rotary dial to set the tens place in a two or three digit number.
The control panel recognizes when a sensor or module is installed. For this reason, sensors
can be assigned any unique address from 1 to 159, and modules can be assigned any unique
address from 1 to 159. There can be a sensor using address 1 and a module using address 1.
0 is an invalid address. In order to set the sensor above address 99, carefully remove the stop
on the upper rotary switch with thumb as shown in example 2.
Example 1:
To select device address 35, turn the ONES rotary dial to
5
and the
TENS
rotary
dial to
3
Example 2:
To select device address 105, turn the ONES rotary dial to
5
and the
TENS
rotary
dial to
10
Figure 7-5 SLC Device Addressing Using Rotary Dials
Figure 7-6
Example 1: Device Set to 35.
Example 2: Device Set to 105.
All dials labeled for ONES
or TENS position.
Summary of Contents for SCSS-700
Page 2: ......
Page 12: ...SCSS 700 Installation Manual 8...
Page 22: ...Model SCSS 700 Installation Manual 1 10 53722...
Page 26: ...Model SCSS 700 Installation Manual 2 4 53722...
Page 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...
Page 42: ...Model SCSS 700 Installation Manual 3 16 53722...
Page 92: ...Model SCSS 700 Installation Manual 4 50 53722...
Page 148: ...Model SCSS 700 Installation Manual 8 26 53722...
Page 192: ...Model SCSS 700 Installation Manual 9 44 53722...
Page 250: ...SCSS 700 Installation Manual A 14 53722...
Page 254: ...Cut Along the Dotted Line...
Page 256: ......
Page 257: ......