PS161-6 Power Supply
Installation Instructions
Overview:
PS161-6 converts a 120VAC / 60Hz input, to a 12VDC or 24VDC nominal output
.
PS161-6 comes with a power-limited power
distribution module with 8 outputs. Class 1 wiring methods and separation of circuits must be considered when connecting DC power supply to the
Delayed Egress hardware.
UL Listings for US Installations:
UL 294 - UL Listed for Access Control System Units.
UL 603 - UL Listed for Power Supplies for Use with Burglar-Alarms Systems.
UL 1481 - UL Listed for Power Supplies for Fire Protective Signaling Systems.
UL Listings for Canadian Installations:
ULC-S318-96 - Power Supplies for Burglar Alarm Systems. Also suitable for Access Control.
Altronix Corp.
140 58th St. Brooklyn, NY
California State Fire Marshal
European Conformity
Specifications:
Input:
Voltage: 120V AC, 60HZ
Current: 3.5A AC
Input fuse ratings:5A/250V
Battery fuse ratings: 7.5A/32V
Output:
Voltage: 20.0-26.4V
Total output: 6 amps
Power limit/output: 2 amps/per channel
Outputs: 8 (For Delayed Egress applications: use only 4)
Ripple voltage: 910mV (Filtered and regulated outputs)
Protection: Thermal and short circuit protection with auto reset overload protection.
Battery Backup
Built-in charger for sealed lead acid or gel type batteries
Maximum charge current 1.54 amp
Automatic switch over to stand-by is instantaneous with no interruption
Enclosure Dimensions: 12.5” x 13” x 3.25” (3.18mm x 330.2mm x 82.55mm)
Fire Alarm Disconnect:
Supervised Fire Alarm disconnect (latching or non-latching) 10K EOL resistor. Operates on a normally open (NO) or normally closed (NC) trigger.
Supervision
AC fail supervision (form “C” contacts).
Visual Indicators
Green AC Power LED indicates 120VAC present.
Additional Features
Short circuit and overload protection.
Unit is complete with power supply, enclosure, battery leads and cam lock.
Enclosure Dimensions
12.5” x 13” x 3.25” (318mm x 330.2mm x 82.55mm)