Mounting and installation
12
252163 / YL560300010
2016-04-20·BA00·III·en·00
Intrinsically Safe Combination Signal -
105 dB (A) / LED Beacon
Series YL5IS
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Independent wiring
• A dual-channel safety barrier or double intrinsically safe connection is required
Loop in/loop out wiring combination device
• A single-channel safety barrier or single intrinsically safe connection is required
• Wires C and D not included in delivery
Two stage alarm
Tone selection of the sound stages
DANGER
Explosion hazard due to selecting the wrong cables!
Non-compliance results in severe or fatal injuries.
• If using separate safety barriers for the sounder and beacon, observe
the cable specifications stated on the selected Zener barrier or on the
isolator certificate.
18056E00
A +v Beacon
B 0v Beacon
C +v Sounder
D +0 Sounder
18057E00
A +v
B 0v
C +v
D 0v
The device has a first and second sound stage.
First sound stage
• Users can select a tone frequency from 32 different variations using the
DIL switch (see diagrams above). Each tone is described in the tone
table.
Second sound stage
• Each first sound stage has a pre-programmed second stage which is
listed in the tone table.
• Users are able to switch between the first and second sound stages by
wiring the unit in one of two ways.
+
-
+
-
5
6
C
D
+
-
+
-
5
6
C
D
Summary of Contents for YL5IS Series