223846 / YA6060300010
2022-07-11·BA00·III·en·05
Mounting and installation
19
DE
EN
FR
IT
ES
RU
NL
DK
SE
FI
PT
GR
PL
CZ
SK
HU
SL
RO
BG
LV
LT
EE
CH
KR
CN
Audible signalling device
Series YA60
7.3.4 Mounting the device
• Carefully insert the connected circuit board.
• Connect the horn flange to the circuit board.
• Set the horn flange on the enclosure. Do not clamp in any cables in the process.
• Insert the horn flange in a straight position without applying any pressure.
• Insert the M5 x 16 cheese-head screws and tighten them to a tightening torque of
3 Nm.
• Re-attach the cover using three PT screws (4.0 x 12) and tighten the screws to a
tightening torque of 0.4 Nm.
7.3.5 Mounting the earth connection
• The device must be provided with a good quality earth connection.
• The internal earth connection is the primary connection point. The external connection
is an additional equipotential bonding conductor and is used where local code or
authorities permit or require such a conductor.
16550E00
Screws and seals
The cheese-head screws are delivered with Nyltite seals.
• Before mounting, check the seals for damage.
• Replace damaged seals.
• Use seals a maximum of 5 times.
• When using screws on a flat surface, note the seal on the screw
head – see figure.