243206 / 857360300020
2016-11-10·BA00·III·en·00
Technical data
7
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
SolConeX extra-low voltage wall-mounting socket
Series 8573/13
5
Technical data
Explosion Protection
Global (IECEx)
Gas and dust
IECEx PTB 16.0029
Ex db eb IIC T6 Gb
Ex tb IIIC T70 °C Db
Europe (ATEX)
Gas and dust
PTB 16 ATEX 1017
E
II 2 G Ex db eb IIC T6 Gb
E
II 2 D Ex tb IIIC T70 °C Db
Certifications and certificates
Certificates
IECEx, ATEX
Technical Data
Electrical data
Rated operational
voltage
max. 50 V
Frequency
0 to 60 Hz (for frequencies > 100 Hz reduction to 12 A required)
Voltage tolerance
-10 ... +6 %
Utilization category
AC-3: 50 V / 16 A
DC-1: 50 V / 16 A
DC-13: 50 V / 16 A
Rated insulation
voltage
550 V
Back-up fuse
without thermal
protection
16 A gG
with thermal
protection
35 A gG
Ambient conditions
Ambient temperature -50 to +60 °C
-40 to +60 °C, optional (silicone-free)
Temperature class
Current
Ambient temperature
T6
16 A [2.5 mm
2
]
Ta = 40 °C
12 A [2.5 mm
2
]
Ta = 55 °C
10 A [2.5 mm
2
]
Ta = 60 °C