7.3.3 Cable Entries
On both sides, the luminaire is equipped with 2 openings each.
All open holes must be closed.
Cable glands and stopping plugs
• depending on version of luminaire, M20 or M25 is available
• must comply with the required IP level of protection.
Please observe the tightening torque for luminaires with installed cable glands and
stopping plugs from R. STAHL Schaltgeräte GmbH.
Luminaires with approved cable glands and stopping plugs; not supplied by
R. STAHL Schaltgeräte GmbH
Please note:
• the required dust resistance!
• the required type of protection!
• the required temperature resistance!
• the IP degree of protection according to the rating plate!
• the operating instructions of the cable glands and stopping plugs!
• the required tightening torques!
• the range of the permissible cable diameter!
Tightening torque
Connection thread
Pressure screw
Cable gland 8161
M20 x 1.5
2.3 Nm
1.5 Nm
M25 x 1.5
3.0 Nm
2.0 Nm
Stopping plugs 8290
M20 x 1.5
1.0 Nm
M25 x 1.5
1.5 Nm
WARNING
Cable glands and stopping plugs which are not approved.
Explosion protection is impaired!
• Only use separately certified cable glands and stopping plugs.