Y05/YL5 INSTALLATION INSTRUCTIONS 

General  Description:  This  application  should  be  installed  and  used  as  recommended  by  the  National  Fire  Protection 

Association standards and practices. 

The  Installer  should  be  familiar  with  these  requirements  together  with  any  local  codes  or  special  requirements  of  the local 

Fire Authority having jurisdiction. 

The  alarm  sounders  are  intended  for  connection  to  the  output  alarm  circuit  of  a  UL  listed  fire  alarm  control  panel only. All 

alarms are compatible with DC line status monitoring. The alarm sounders are suitable for outdoor use (-35ºC to +66ºC). 

Installation procedures must confirm to appropriate agency requirements including but not limited to the following:- 

 

NFPA72E, NEC ART.760 ET.AL., CAN/ULC-S524-M86, CEC PART 1 SEC 32 

Installation:  The  sounder  can  be  affixed  to  most  surfaces  using  screws  through  the  external  mounting  lugs  or  by  drilling 

internal fixing holes. A 20mm gland entry is provided for the supply cable. The cable and gland must be fitted in accordance 

with the national and local regulations. It is not necessary to earth the sounder circuitry but earth tags should be used if earth 

continuity of conduit or cable sheathing needs to be maintained. 

Supply input: Ensure that the supply is correct for the voltage rating of the sounder or combined sounder strobe being 

installed. Ensure the supply is OFF before making any connection and wire only in accordance with the terminal label detail.  

Sound selection: Ensure the supply is OFF before proceeding. All dc and ac units have selectable alarm sounds (see table 

below  for  details)  and  are  selectable  by  means  of  a  5  way  dil  switch  SW1.  A  second  sound  is  made  available  upon  the 

application of a third wire connected to terminal TB1/3 as shown in Fig. 1 while still connected to terminal TB1/2. Alternatively 

1st  and  2nd  stage  sound  signals  can  be  generated  by  supply  reversal  (FOR  DC  UNITS  ONLY)  see  Fig.  2.    Independent 

second stage sound is available by using SW2 (OPTIONAL- only fitted with orders).  

WARNING - Loud alarm sound. Wear ear defenders when testing, installing and commissioning. 

SOUND SELECTION TABLE

 

 

First Stage Sound  

 

frequency   

rept. 

 

Second 

 

switches   

 

 

 

 

 

 

 

 

Hertz   

 

rate 

 

Stage   

 

1 2 3 4 5 

 

Special Application 

 

1  Alternate two-tone 

 

800-1000   

0.5   

 

 

 

 

1 1 1 1 1 

 

Fire Alarms 

2 Alternate two-tone 

 

2500-3100   

0.5   

 

 

 

 

0 1 1 1 1 

 

Security Alarms 

3 Alternate fast two-tone 

800-1000   

0.25 

 

 

 

 

1 0 1 1 1 

 

Increased urgency   

4 Alternate fast two-tone 

2500-3100   

0.25 

 

 

 

 

0 0 1 1 1 

 

Security deterrent 

5 Alternate two-tone 

 

440-554 

 

0.4/0.1   

14   

 

 

1 1 0 1 1 

 

AFNOR, France 

6 Alternate two-tone 

 

430-470 

 

1.0   

 

14   

 

 

0 1 0 1 1    

7 Alternate v.fast two-tone  800-1000   

0.13 

 

12   

 

 

1 0 0 1 1 

 

 

8 Alternate v.fast two-tone  2500-3200   

0.07 

 

13   

 

 

0 0 0 1 1 

 

 

9 Alternate two-tone 

 

440-554 

 

2.0   

 

10   

 

 

1 1 1 0 1 

 

Turn-out, Sweden 

10 Continuous note  

 

700  

 

 

 

 

 

 

 

0 1 1 0 1 

 

All-clear, Sweden 

11 Continuous note  

 

1000 

 

 

 

 

31   

 

 

1 0 1 0 1 

 

 

12 Continuous note  

 

1000 

 

 

 

 

 

 

 

0 0 1 0 1 

 

 

13 Continuous note  

 

2300 

 

 

 

 

 

 

 

1 1 0 0 1 

 

 

14 Continuous note  

 

440  

 

 

 

 

 

 

 

0 1 0 0 1 

 

 

15 Interrupted tone  

 

1000 

 

 

2.0   

 

31   

 

 

1 0 0 0 1 

 

 

16 Interrupted tone  

 

420  

 

 

1.25 

 

30   

 

 

0 0 0 0 1 

 

AS2220, Australia 

17 Interrupted tone  

 

1000 

 

 

0.5   

 

 

 

 

1 1 1 1 0 

 

 

18 Interrupted tone  

 

2500 

 

 

0.25 

 

 

 

 

0 1 1 1 0 

 

 

19 Interrupted tone  

 

2500 

 

 

0.5   

 

 

 

 

1 0 1 1 0 

 

 

20 Interrupted tone  

 

700  

 

 

6/12 

 

10   

 

 

0 0 1 1 0 

 

Pre-vital mess, Sweden 

21 Interrupted tone  

 

1000 

 

 

1.0   

 

32   

 

 

1 1 0 1 0 

 

 

22 Interrupted tone  

 

700  

 

 

4.0   

 

10   

 

 

0 1 0 1 0 

 

Air-raid, Sweden 

23 Interrupted tone  

 

700  

 

 

0.25 

 

10   

 

 

1 0 0 1 0 

 

Local warning, Sweden 

24 Interrupted tone  

 

720  

 

 

0.7/0.3   

10   

 

 

0 0 0 1 0 

 

Industrial alarm, Germany 

25 Int,fast,rising volume 

1400 

 

 

0.25 

 

26   

 

 

1 1 1 0 0    

 

26 Fast siren 

 

 

 

250-1200   

0.085   

11   

 

 

0 1 1 0 0 

 

 

27 Rising constant, fall   

1000 

 

 

10/40/10 

17   

 

 

1 0 1 0 0 

 

Industrial alarm, Germany 

28 ISO 8201 Evacuation 

800-1000   

as std   

11   

 

 

0 0 1 0 0 

 

Int’l evacuation alarm 

29 Fast whoop   

 

 

500-1000   

0.15 

 

32   

 

 

1 1 0 0 0 

 

 

30 Slow whoop  

 

 

500-1200   

4.5   

 

12   

 

 

0 1 0 0 0 

 

Evacuation, The Netherlands 

31 Reverse sweep   

 

1200-500   

 

 

11   

 

 

1 0 0 0 0 

 

Evacuation, Germany 

32 Siren 

 

 

 

 

500-1200   

3.0   

 

26   

 

 

0 0 0 0 0 

 

switch settings: ON=1 and OFF=0 

MOUNTING: The Y05 series alarm units are mounted to a wall or bulkhead of suitable material using the lugs projecting from the 

side of the case. The lugs are bored 8mm clearance on 153mm centres. The recommended length of fixing screws is 25mm. To 

maintain the integrity of the weather seal, the cable entry must be via a suitable sealed gland.    

 

 

D7426/4

 

 

 