Technical Data
10
162277 / 9440607310
2018-08-13·BA00·III·en·06
CPU & Power Module for Zone 1 / Div. 1
Series 9440/22, 9490
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Technical Data
Design
9440/22-01-11 (24 V DC)
9440/22-01-21 (90 to 253 V AC)
Electrical data
Auxiliary power
Nominal voltage
24 V DC
120 V / 230 V AC
Voltage range
20 to 35 V DC
90 to 253 V AC
Mains frequency
–
50 / 60 Hz
Frequency range
–
45 to 66 Hz
Current
consumption
without
I/O modules
approx. 0.21 A at 24 V DC
approx. 25 mA at 230 V AC,
approx. 48 mA at 120 V AC
with
8 I/O modules
approx. 2.5 A at 24 V DC
approx. 0.4 A at 230 V AC,
approx. 0.8 A at 120 V AC
Power dissipation
without
I/O modules
5 W
8.4 W
per I/O module
approx. 1.4 W
approx. 1 W
Polarity reversal
protection
yes
not applicable
Undervoltage
monitoring
yes
yes
Interfaces for
fieldbus, redundant
fieldbus and
ServiceBus
Interface
RS485-IS acc. to Profibus specification
Cable length /
Transfer rate
Copper cable
1200 m with 9.6 ... 93.75 kbit/s
1000 m with 187.5 kbit/s
400 m with 500 kbit/s
200 m with 1.5 Mbit/s
Fibre optic
cable
approx. 2000 m with 1.5 Mbit/s
ServiceBus
1200 m with 9.6 kbit/s
Line termination
powered resistor (termination resistor is installed in the Sub-D plug,
see accessories)
Address range
0 ... 127
Redundancy
Full redundancy and line redundancy