Safety temperature monitor and limiter
Series 8146/5041-STW, 8146/5041-STB,
8146/5051-STW+STB
7.2.3 Transport Protection for Holes
7.2.4 Operating Position
7.3
Installation
DANGER
Explosion hazard due to leaking holes!
Non-compliance results in severe or fatal injuries.
• Open holes protected with an adhesive tape must be sealed by
means of adapted and certified components.
• Remove the adhesive tape completely.
• Make sure that the components comply with the IP-protection.
16523E00
• Alignment of enclosure
depending on mounting type:
• For vertical mounting:
any alignment
• For horizontal mounting:
cover on top
• Hanging position/overhanging
cover is not permitted!
DANGER
Explosion hazard due to impermissible cable entries!
Non-compliance results in severe or fatal injuries.
• Only use cable entries approved for the required type of protection.
• When selecting cable entries, observe the thread type and thread
size in the equipment documentation.
• Make sure that the conductor diameter matches the clamping
cross-section of the cable entries.
DANGER
Explosion hazard due to incorrectly laid cables in the Ex e enclosure!
Non-compliance results in severe or fatal injuries.
• Adhere to the required creepage distances and clearances.
• Fasten mounting rails or elements properly.
≦ 90°