Commissioning
WARNING
Danger of electric shock due to energised parts!
Non-compliance can result in severe or fatal injuries.
• All connections and wiring must be disconnected from the power supply.
• Secure the connections against unauthorized switching.
Connection type
Connection terminals
Connection cross-
section
solid / finely
stranded
0.75 ... 2.5 mm
2
One or two conductors can be installed to one connection terminal.
Both conductors must have the same cross-section and must be
made of the same material. The conductors can be connected
without previous measures.
In case of different conductor cross-sections 1.5 ... 2.5 mm
2
solid/finely stranded, only 1 conductor each of the different
conductor cross-sections may be installed under the connection
terminal. The conductors must be made of the same material.
Suitable conductors
09187E00
solid
09188E00
stranded
09189E00
finely stranded
Tightening torque 1.2 Nm (connection terminals)
05899E00
8082/2 conductor connection
DANGER
Explosion hazard due to incorrect installation!
Non-compliance results in severe or fatal injuries.
• Check the device for proper installation and function before
commissioning.
• Comply with the national regulations.