Compact Sheet-steel 

Emergency Light Fitting

Series 6118/1

Further error indications will be reset directly after troubleshooting.

If the error cannot be eliminated using the mentioned procedures:

• Contact R. STAHL Schaltgeräte GmbH.

For fast processing, have the following information ready: 

• Type and serial number of the device

• Purchase information 

• Error description 

• Intended use (in particular input / output wiring)

11

Maintenance and repair

11.1 Maintenance

• Consult the relevant national regulations to determine the type and extent of  

inspections.

• Adapt inspection intervals to the operating conditions.

During maintenance of the device, check at least:

• the tight fit of the clamping screws holding the cables,

• if the device enclosure and / or protective enclosure have cracks or other visible signs 

of damage,  

• the seals for ageing and damage, 

• the device inside and outside for pollution and clean it if neccessary,

• compliance with the permissible temperatures (according to EN 60079),

• if the device is used in accordance with its designated use.

Resetting the capacity error (blinking red).

• Replace the battery.

Automatic:

• A continuous operation test is carried out automatically after 36 hours.

• The error will be reset once the test has been passed successfully.

Manual:

• Actuate the switch in the battery case for 5 seconds.

• Release the switch.

• Actuate the switch twice within 10 seconds for a duration of 2 seconds.

• Close the battery case.

• Resetting of the capacity error will be indicated on the LED display for 

5 seconds by blinking red/green.

• The error is reset.

WARNING

Risk of electric shock or malfunctioning of the device due to unauthorized 

work!

Non-compliance can result in severe injuries and material damage.

• Work performed on the device must only be carried out by appropriately 

authorized and qualified electricians.

• To be carried out as per EN60079-17 and as per EN60079-19.

Summary of Contents for 6118/1 Series

Page 1: ...EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN Operating instructions Additional languages r stahl com EN Compact Sheet steel Emergency Light Fitting Series 6118 1...

Page 2: ...2 Safe use 5 3 3 Intended Use 5 3 4 Modifications and alterations 6 4 Function and device design 6 4 1 Function 6 4 2 Device design 7 5 Technical data 7 6 Engineering 10 6 1 Mains operation 10 6 2 Eme...

Page 3: ...ates and EU Declaration of Conformity r stahl com The device has IECEx approval For certificate please refer to the IECEx homepage http iecex iec ch Further national certificates can be downloaded via...

Page 4: ...ICE Type and source of danger damage Consequences of danger Taking countermeasures to avoid the danger or damage Symbol Meaning Tips and recommendations on the use of the device Danger due to explosiv...

Page 5: ...ion Observe national assembly and installation regulations e g IEC EN 60079 14 Observe national safety and accident prevention regulations During installation and operation observe the information cha...

Page 6: ...nd closed remote switch the light fitting switches to emergency light operation and the lamp is supplied with voltage and power for a set period of time via the integrated battery The light fitting au...

Page 7: ...a 18248E00 1 Cable gland 6 Luminaire enclosure 2 Glass pane 7 Seal 3 Reflector plate 8 Lamp holder 4 Ballast 9 Central lock 5 Battery 10 Stopping plug Explosion Protection Global IECEx Gas and dust IE...

Page 8: ...losure Sheet steel powder coated white similar to RAL 9016 Stainless steel SS316L V4A 1 4404 brushed Lens Safety glass Seal Foamed silicone seal in luminaire enclosure Luminaire locking Central lockin...

Page 9: ...oth sides of the luminaire for mounting of wall mounting brackets Recessed light fitting Variant 1 mounting frame attached to enclosure using M6 screws Variant 2 mounting frame welded to enclosure Not...

Page 10: ...y Light Fitting Series 6118 1 6 Engineering 6 1 Mains operation 6 1 1 Stand by operation The light fitting is switched off 6 1 2 Continuous operation The light fitting is switched on 6 1 3 Normal ligh...

Page 11: ...6043 7 The following connection versions are possible Point to point connection Linear connection 16400E00 Remote switch is closed Remote switch is opened Power supply operation Switching on the lamps...

Page 12: ...materials Handle with care Store protected from fire sources of dust harmful gases and liquids Store in a dry and cool location Recommendation Store battery at an ambient temperature of 5 to 25 C and...

Page 13: ...s not affected due to external influences i e pressure conditions chemical mechanical thermal and electric impact such as vibration humidity and corrosion see IEC EN 60079 14 The device must only be i...

Page 14: ...out with fastening set for wall and ceiling mounting A Insert nut sealed with blind plug Dimensional drawings All dimensions in mm inches Subject to modifications 521 20 51 25 0 98 6 x 10 6 x 0 39 65...

Page 15: ...es DANGER Explosion hazard due to inadmissible heating Non compliance results in severe or fatal injuries Avoid external heat sources and or direct sunlight risk of change of temperature class or chan...

Page 16: ...teel Emergency Light Fitting Series 6118 1 8 2 1 Frame mounitng 8 2 2 Mounting bracket Example Assembly of mounting bracket All other brackets are mounted as shown in the example 17247E00 Mount the fr...

Page 17: ...EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN Compact Sheet steel Emergency Light Fitting Series 6118 1 8 2 3 Ring Bolt Assembly 18291E00 Screw the 2 ring eyes into the mounting part Attach the mounti...

Page 18: ...results in severe or fatal injuries Open luminaires without switch only in de energized state see information plate on the lock 18242E00 18245E00 18244E00 Remove the closing cap 11 of the central loc...

Page 19: ...st being switched on again Version with switch The luminaire is positively disconnected from the power supply by actuating the central lock In open end position and with translucent cover swivelled do...

Page 20: ...carried out precisely Do not clamp any part of the conductor insulation Do not interchange the conductors Observe the technical regulations when connecting the conductor Clamp the conductor firmly Do...

Page 21: ...ngth 10 11 mm 16333E00 16408E00 The connection to the battery is interrupted Before commissioning connect the battery NOTICE Deep battery discharge due to non utilisation Non compliance may lead to ma...

Page 22: ...lowing the required dust resistance the required type of protection the required temperature resistance the IP degree of protection according to the rating plate the operating instructions of the cabl...

Page 23: ...g plugs have been tightened firmly Check if all conductors have been clamped firmly Check if the line voltage and the rated operational voltage are consistent Check if the permissible conductor diamet...

Page 24: ...e operation mode of the selected emergency light operating time Emergency light operation time Stand by operation The lamp is switched off regardless of normal lighting Continuous operation The lamp i...

Page 25: ...of the lamps and the battery Continuous operation test starts within 44 days after commissioning is carried out every 365 days discharges the battery up to the final discharge voltage checks the func...

Page 26: ...Light fitting is ready for operation blinking green Light fitting is ready for operation Function or continuous operation test is activated Red Error Battery is defective or electric circuit is interr...

Page 27: ...e cracks or other visible signs of damage the seals for ageing and damage the device inside and outside for pollution and clean it if neccessary compliance with the permissible temperatures according...

Page 28: ...ff the lamp at the end of the service life CAUTION Danger of electric shock due to energised parts Non compliance can result in minor injuries All connections must be disconnected from the power suppl...

Page 29: ...the form and send it Confirmation will be sent R STAHL s customer service will contact you You will receive an RMA form after speaking with customer service Send the device along with the RMA form in...

Page 30: ...are parts CAUTION Danger due to chemical reactions Human health and the environment are at risk Batteries collect them separately dispose of them in controlled fashion do not dispose of them in the do...

Page 31: ......

Reviews: