Commissioning
7.1
Checking Mounting and Installation
Check the device for the following:
▶
External damage
▶
Correct, secure fit on the BusRail
▶
Specified tightening torque of the safety screws (Torx) (1.2 Nm)
7.2
Adjusting the Communication Protocol and Station Address
▶
Remove the 9442/32 CPU module (if equipped), see the "Dismounting" chapter in the
9442/32 CPU operating instructions.
Rotary switch S1 to S3
The rotary switches S1 to S3 are located on the left slot (slot 0) on the socket below the CPU;
see the figure. This protects them from being subjected to unauthorised modification during
operation. The rotary switches S1 to S3 are at position 0 when delivered.
▶
During realignment, select the communication protocol for each S1 rotary switch as
follows; see the table
1)
HEX rotary switch (0 to F) from HW rev. C
18454E00
19049E00
The figure shows the socket with three slots as an example.
The arrangement of the rotary switches is also valid for the socket with four slots.
Communication protocol
Rotary switch S1
Rotary switch S1
from rev. C
1)
Reserved
0
0
PROFIBUS PNO (Red.)
1
1
PROFIBUS Stahl Red. Addr. Offs. 1
2
2
PROFIBUS Stahl Red. Addr. Offs. 0
3
3
PROFINET
4
4
Reserved
5
5
Modbus TCP
6
6
EtherNet/IP
7
7
Reserved
8
8
Reserved
9
9
Reserved
–
A
Reserved
–
B
Reserved
–
C
Reserved
–
D
Reserved
–
E
Reserved
–
F