COMMAND
VALUE
DESCRIPTION
No Command
** ON **
Turns the current MPS ON.
** OFF **
Turns the current MPS OFF.
ON DELAY
0 < t < 18:12:15
Delays MPS START time for a specified period after it would normally start
Min Time ON
0 < t < 18:12:15
When in an ON cycle, the MPS will be ON for at least this long
Min Time OFF
0 < t < 18:12:15
When in an OFF cycle, the MPS will be OFF for at least this long
Max Time ON
0 < t < 18:12:15
When in an ON cycle, the MPS will be ON for at most this long
Max CTime ON
0 < t < 18:12:15
When in an ON cycle, the MPS will be ON for at most this long.
The length of ON time is calculated once at the start.
Time ON ONCE
0 < t < 18:12:15
When in an ON cycle, the MPS will be ON for this long.
Overfeed
0 < t < 18:12:15
An MPS will not be ON longer than this between over feed clearing times,
as setup in the General window.
Set Overfeed
0 < t < 18:12:15
An MPS will not be ON longer than this time unless the measurement is
within 5% of the set point.
ON If Time>
0 < t < 23:59:58
The MPS will turn ON if the time is greater than this.
OFF If Time>
0 < t < 23:59:58
The MPS will turn OFF if the time is greater than this.
ON If Time<
0 < t < 23:59:58
The MPS will turn ON if the time is less than this.
OFF If Time<
0 < t < 23:59:58
The MPS will turn OFF if the time is less than this.
ON/OFF If pH >,<
0.00 < x < 9.99
The MPS will turn ON/OFF depending on the pH.
ON/OFF If ORP >,<
0 <x< 999
The MPS will turn ON/OFF depending on the ORP.
ON/OFF If PPM >,<
0.00 <x< 9.99
The MPS will turn ON/OFF depending on the PPM.
ON/OFF If Temp >,<
31.9 <x< 211.9
The MPS will turn ON/OFF depending on the temperature.
ON/OFF If Press>, <
0.0 <x< 99.9
The MPS will turn ON/OFF depending on the pressure.
COMPUTE MPS
1 <x<43
The MPS will jump to the indicated MPS and compute it first
ON If Alarm ON
The selected module indicates which alarm this is based ON.
OFF If Alarm ON
The selected module indicates which alarm this is based ON.
ON If Overfeed
1 <x< 24
The MPS will turn ON if the overfeed timer has been reached for
the indicated MPS.
ON If SET ALRM
0 <x< 24
The set point alarms are calculated from the alarm percentage. The MPS
will be ON if the indicated set point alarm is ON.
NOTE:
the indicated MPS must have already been computed.
Date ON/OFF
1 <x< 31
The MPS will turn ON/OFF depending on the day of the month
WKday ON/OFF
0 <x< 6
The MPS will turn ON/OFF depending on the day of the week. 0 = Sunday,
6 = Saturday.
ON/OFF If MPS
0 <x< 24
The MPS will turn ON/OFF depending on the indicated MPS.
ON/OFF
NOTE:
The indicated MPS must have already been computed.
ON/OFF If Sw
0 <x< 5
The MPSs will turn ON/OFF depending on the indicated flow switch. Only
ON/OFF
module 3 can have 5 switches; the others can have 3 each.
Sequences ON
Will set the sequence state to the indicated sequences.
CntR=0@Midnight,
Clears the counter at midnight. Each MPS has a counter keeping track of
how many times it turns ON.
Cntr=0 ON Date
0 <x< 31
Clears the counter at the start of the indicated date.
ON/OFF If Cntr >
0 <x< 65535
The MPS will turn ON/OFF depending on the count.
Prop GON
0 <x< 65535
The MPS will use this gain for calculating the proportional feed time on
the ON time.
Prop GOFF
0 <x< 65535
The MPS will use this gain for calculating the proportional feed time on
the OFF time.
Manual ON Time
18:12:15
This is the time the MPS will be ON when turned ON in the manual mode
from the service menu.
ON/OFF If dPress>,<
0 <x< 99.9
The MPS will turn ON/OFF depending on the differential pressure.
Appendix C: Programming Command List
The output from the mini-programs (MPSs) controls the state of the relays, alarms, and pagers. Each MPS is made up of up
to 20 commands from the following list.