Prescott Series Installation Manual
Page 9
VENTING: THROUG COMBUSTIBLES
Figure 2
Figure3
Corner
Installation
Through
the
Wall
Installation
Note A: Double wall PL vent requires a minimum of three inch (3”) clearance to combustibles and the use
of a listed wall thimble, fire stop or roof flashing where applicable.
ATTENTION: We strongly recommend using a battery backup system if the pellet stove is installed
using horizontal venting only. This prevents any smoke from entering your home in the event of a
power failure.
Legend for Figures 2 through 5
A. 45 degree elbow
I. PL Vent Fire Stop
B. Thimble
J. Roof Flashing
C. PL Vent Section
K. Storm Collar
D. Stove Exhaust Pipe
L. Rain Cap
E. Air Intake Damper
M. Outside Air Pipe
F. Air Vent Damper
N. PL Vent Section
G. 90 degree elbow
O. Wall Band
H. 45 degree elbow
P. Outside Air Inlet Cover
1.
PL vent may be installed directly through a combustible wall, ceiling or roof according to PL vent
manufacturer’s instructions. (See Figures 2 and 3).
2. The PL vent system must be properly sealed and secured as per PL vent manufacturer’s specifications.
An airtight seal is necessary in connecting the vent to the stove. Using a PL Vent pipe adapter, secure the
PL vent with at least three sheet metal screws and high temperature silicone adhesive, (RTV), or metal
tape at each joint.