WWW.SSTCOMM.COM
3
2 Product Overview
2.1 Product Function
IOT600-TWX-TS is designed to get ThingWorx users connected to their Modbus RTU slave, Modbus TCP
slave and Modbus TCP Master devices with just a few minutes of configuration time. The gateway could be edge
gateways that securely connect industrial Modbus equipment over Ethernet networks to ThingWorx.
2.2 Product Features
[1] Support maximum number of properties:1000 (Encrypted communication:860);
[2] The communication mode adopts the WebSocket mode and support TLS encrypted transmission;
[3] Modbus RTU master
Support connecting 15 Modbus slaves
Each serial port supports up to 100 Modbus commands
Support baud rate:1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200bps
Support 01H, 02H, 03H, 04H, 05H, 06H 0FH and 10H function codes
[4] Modbus TCP master
Support up to 100 Modbus commands and up to 36 Modbus TCP devices
Support 01H, 02H, 03H, 04H, 05H, 06H 0FH and 10H function codes
[5] Modbus TCP slave
Support 01H, 02H, 03H, 04H, 05H, 06H 0FH and 10H function codes and up to 36 Modbus TCP master
Register supports int16, uint16, int32, int32 inverse, uint32, uint32 inverse, float, float inverse, double,
double inverse, int64, int64 inverse, uint64, uint64 inverse
Support coil status block, input status block, hold register block and input register block, each block
supports the maximum 1024 registers or bits
[6] Power supply: 24VDC (9V ~ 30V), 90mA (24VDC);
[7] Working temperature: -4
℉
~140
℉
(-20
℃
~60
℃
), relative humidity: 5% ~ 95% (non-condensing);
[8] External Dimensions (W*H*D): 1.57 in*4.92 in*4.33 in (40mm*125mm*110mm);