Industrial Ethernet Serial Gateway
(
Modbus RTU/ASCII / Modbus TCP
)
Modbus Serial/TCP Series
User Manual
REV 1.4
SST Automation
E-mail:
[email protected]
WWW.SSTCOMM.COM
Page 1: ...Industrial Ethernet Serial Gateway Modbus RTU ASCII Modbus TCP Modbus Serial TCP Series User Manual REV 1 4 SST Automation E mail support sstcomm com WWW SSTCOMM COM...
Page 2: ...t 13 3 2 2 IP search 14 3 3 Configuration 16 3 3 1 Mode selection 17 3 3 2 Ethernet parameters 18 3 3 3 Serial parameters 18 3 3 4 ID mapping Advanced parameters 20 3 3 5 Modbus parameters Advanced pa...
Page 3: ...User Manual Industrial Ethernet Serial Gateway Modbus Serial TCP Series WWW SSTCOMM COM 3 5 2 Installation Method 34...
Page 4: ...y products type list Product Type Ethernet end protocol Serial protocol Serial number GT200 MT RS Modbus TCP Modbus RTU ASCII Single serial port GT200 MT 2RS Modbus TCP Modbus RTU ASCII Dual serial po...
Page 5: ...simultaneously and can support 32 command request simultaneously 2 Master mode Support visiting 4 different IPs or Modbus TCP slaves of different ports 3 Every serial interface is all RS485 or RS232 h...
Page 6: ...dware Description 2 1 Appearance Notes 1 The picture above shows the appearance of GT200 MT 2RS 2 GT200 MT 2RS two serial ports serial I and serial II 3 GT200 MT RS one serial port serial I Dual Ether...
Page 7: ...nnection has been established Blinking Green Slave mode Modbus TCP no connection Master mode Modbus TCP connection has not been established Blinking Red Modbus TCP connection is disconnected and no lo...
Page 8: ...f Run mode forbidding reading and writing of configuration data configuration data protection switch On On Firmware update mode IP address is 192 168 0 10 this mode can only update firmware Notes Rest...
Page 9: ...24V Power interface 2 4 2 Ethernet interface Ethernet interface uses RJ 45 connector its pin standard Ethernet signal is defined as below Pin Signal Description S1 TXD Tranceive Data Output S2 TXD Tra...
Page 10: ...ignal Description 1 TX connect with RX of user device 2 RX connect with TX of user device 3 GND Pin of RS485 interface is defined as below D D GND 1 2 3 Pin Signal Description 1 D RS485 2 D RS485 3 GN...
Page 11: ...bsection without repeater and can up to 127 stations with RS485 repeater Plug connection 3 pin pluggable terminal 2 The main points on RS485 transmission equipment installation All the equipment are c...
Page 12: ...es gateway is 192 168 0 10 subnet mask is 255 255 255 0 and gateway address is 192 168 0 1 When users click the Advanced tab in the Restore Factory Settings the default IP address configuration is DHC...
Page 13: ...s of Modbus Serial TCP users need to search the gateway using the software The software provides two ways to search the gateway 3 2 1 Search all equipment in Ethernet Click Search Equipment button of...
Page 14: ...nual Industrial Ethernet Serial Gateway Modbus Serial TCP Series WWW SSTCOMM COM 14 3 2 2 IP search Click IP Search button of the main interface will pop up a dialog box which demands you to input IP...
Page 15: ...Modbus Serial TCP Series WWW SSTCOMM COM 15 After entering the correct IP address the software will search Modbus Serial TCP series gateway with this IP address in the network and list the informatio...
Page 16: ...h equipment 3 3 Configuration Select the equipment to be configured in the list and the Locate Configuration Remote Reset New Open and Save buttons will become available Click Configuration button a p...
Page 17: ...P salve through the gateway Modbus ASCII slave mode Modbus TCP master communicate with Modbus ASCII slave through the gateway Modbus ASCII master mode Modbus ASCII master communicate with Modbus TCP s...
Page 18: ...tinguish from other equipment Assign IP Mode set the IP address configuration mode of the equipment IP address set IP address of the equipment Subnet Mask set subnet mask of the equipment Default Gate...
Page 19: ...y None Odd Even Stop bit 1 2 Data bit 8 currently only support 8 data bits Notes GT200 MT 2RS gateway You only need to set one serial port if all serial port parameters are consistent and then click A...
Page 20: ...Offset of Slave ID D value of virtual ID and actual ID can be negative Actual Salve ID by clicking Set button to calculate When selecting RTU ASCII slave mode users need to specify the serial port to...
Page 21: ...o 4 group ID mapping 3 3 5 Modbus parameters Advanced parameters When you select RTU slave or ASCII slave mode and only configure the basic parameters the item does not need to be configured Set Time...
Page 22: ...you can set priority of frames After enabling Priority Control users can set the parameters they want and only RTU ASCII salve mode supports the function Specify the master the requests of specified...
Page 23: ...e and only configure the basic configuration this cannot be configured Advanced parameters include Password Confirm Password Use default port Port Number Start up Delay of Serial Port Restore Factory...
Page 24: ...nd Keep Alive When a TCP connection idle time reaches the set value if Keep Alive is selected then transmit keep alive message If not then disconnect the TCP connection Limitation of communication IP...
Page 25: ...download to the equipment 2 Cancel Yes Save to the hard drive and close No No save and direct close 3 Help Open the software manual 3 4 Locate When users manage multiple Modbus Serial TCP gateways you...
Page 26: ...is restarting the selected equipment Click remote reset ENS and SNS red indicators will be on at the same time Select the equipment in the list first click Remote reset button it will pop up a confir...
Page 27: ...Open online as shown below is equivalent to import select the device from the list click the Open if the equipment type of the gateway is the same with the opened configuration file type and the equi...
Page 28: ...Industrial Ethernet Serial Gateway Modbus Serial TCP Series WWW SSTCOMM COM 28 3 8 Save Save is equivalent to export select a device and click Save save the parameters of the device as inf format on t...
Page 29: ...rial Gateway Modbus Serial TCP Series WWW SSTCOMM COM 29 Notes The configuration file can be opened with notepad you can modify the data inside make sure the accuracy of the modified data Please don t...
Page 30: ...t number of equipment needs to be connected the default value is 502 Function support function code 1 2 3 4 5 6 15 and 16 Slave ID the slave address virtual ID Start Address the start address of regis...
Page 31: ...communication between Ethernet and serial devices The following is some typical application of Modbus Serial TCP series gateway Take GT200 MT 2RS as an example 4 1 Multiple Ethernet master connect wi...
Page 32: ...User Manual Industrial Ethernet Serial Gateway Modbus Serial TCP Series WWW SSTCOMM COM 32 4 2 Multiport serial master connect with multiple Ethernet slave...
Page 33: ...Ethernet Serial Gateway Modbus Serial TCP Series WWW SSTCOMM COM 33 4 3 Serial master connect with serial slave via Ethernet Serial devices communicate via Ethernet not subject to the limitation of th...
Page 34: ...Industrial Ethernet Serial Gateway Modbus Serial TCP Series WWW SSTCOMM COM 34 5 Installation 5 1 Machine Dimension Size 1 57 in width 4 92 in height 4 33 in depth 5 2 Installation Method 35mm DIN ra...
Page 35: ...User Manual Industrial Ethernet Serial Gateway Modbus Serial TCP Series WWW SSTCOMM COM 35...