Baud Rate - 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200, 230400;
Data Bits - 8 (currently only support 8 data bits);
Check Bit - None, Odd, Even, Mark, Space;
Stop Bits - 1, 2;
Transmission mode -RTU;
Response timeout - When the Modbus master send commands, the time waiting for response from the
slave, the range is 300~60000ms;
Delay between polls - After one Modbus command has been sent and has received correct response, the
delay time before next command being sent, the range is: 0 ~ 2500ms;
Output Mode - Modbus write command (command output) has two output modes: cycle and change of
value output;
Change of Value: When the output data has changed, it outputs the write command and stop outputting
after receiving correct response;
Cycle: the same with Modbus read command output mode, and output according to the scan rate;
Scan rate - Ratio of slow scan cycle to fast scan cycle;