3rd Floor, building 1, Zaimao industrial park, Baoji road, Bantian, Longgang district,
Shenzhen City, China Post code: 518049
Frequency Signal Transducer
Istructions
CE-F01-**MS*-0.5
1 Overview
This product is an arbitrary waveform of the frequency signal
detection
isolation
transducer.
Using
the
principle
of
photoelectric
isolation can convert
the input frequency signal into
a linear output of 0 ~ 5V, 0 ~ 20mA, 4 ~ 20mA and other standard
signals.
The input frequency signal can be a sine wave, square
wave and zero-crossing wave, and its amplitude can reach
1000Vpp.
This product is double-isolation, the input and output
are isolated from the power supply. Product installation is simple,
can be widely used in communications, power, railway, industrial
control and other fields.
Features:
Ø
With waveform shaping function, can be arbitrary
waveform input measurement;
Ø
Amplitude variation can be as low as 5%;
Ø
Frequency measurement up to 10KHz;
Ø
Good stability and high precision.
2 Case Style
Figure 1, DC power supply (MS2) product appearance
Figure 2, 220V power supply (MS2) product appearance
3 Part Number
Figure 3 Product Selection Guide
4 Specifications
Test conditions: auxiliary power: +12 V, room temperature: 25
°
C.
Input range: frequency: 0-50Hz~10KHZ, Amplitude: 5-500V;
Output: 0-5V, 0-20mA, 1-5V, 4-20mA, 0-10V;
Power supply: DC 12V,15V,24V,AC/DC 85V
~
265V;
Accuracy: 0.5;
Load capacity:
≥
2K
Ω
(voltage output);
≤
250
Ω
(current output);
Temperature drift: <500ppm/
°
C;
Isolation voltage: DC 2500V
Response time:
≤
200 mS;
(Frequency <100Hz response time
<800mS)
Rated power consumption: <0.5W
Output ripple: <10mV
Frequency range: 0Hz
~
10kHz
Surge Immunity: Input 4KV (L-N / 2
Ω
/ integrated wave),
power supply / output port 2KV (L-N / 40
Ω
/ integrated wave);
Impulse immunity:
±
2KV input / power port, analog I / O port
±
1KV;
Input overload capacity: continuous overload: 120%; short-term
overload: 2 times the rated voltage input value for 1 second;
Operating temperature: -10
°
C~+60
°
C;
Storage conditions: -40
°
C~+70
°
C.
5 Connections Diagram
Figure 4, wiring diagram of CE-F01-3 * MS2 / CE-F01-8 * MS2
Figure 5, wiring diagram of CE-F01-4 * MS2 / CE-F01-5 * MS2